Page 858 - Din prodcuts 2020
P. 858

9/28             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          SMISSLINE TP plug-in system
          RCBOs FS403 series       10 000 -  6000  A  y  type and
          short time delay Type F


                                                               FS403
                                    Rated voltage Un           240/415V
                                    Number of poles            4
                                    Rated frequency fn         50/60 Hz
                                    Rated breaking capacity Icn  10 kA (10 A to 16 A)
                                                               6 kA (20 A to 32 A)
                                    Current limitation class   3
                                    Total cut-off time acc. to EN 61009
                                    at In                      40 ms
           FS 403 M
                                    at 5x In                   25 ms
                                    Connection cross-section   max. 25 mm  flexible wire with wire end sleeve
                                                                       2
                                    Terminal at load side      Possible to connect 2 wires in one chamber.
                                                               Both chambers could be used with two different
                                                               cross-sections.
                                    Tightening torque          2.8 Nm
                                    Degree of protection       IP20
                                    Endurance                  >5000
  9
                                    Resistance to climate      EN 61009
                                    Ambient temperature        –25° C … +40° C
                                    Mounting position          any
                                    Vibration resistance       EN 61009
                                    Plastic parts              halogen-free
                                    Contacts                   cadmium-free
                                    Standard                   EN61009-1, SEV, VDE
                                    Accessory:
                                    Auxiliary- and signal contacts are to attach on to the left of the device through the customer.
                                    Please notice:
                                    For the influence of the ambient temperature and the thermal influences of row mounted RCBO’s it is necessary to calculate
                                    with the same correction factors like with MCBs.
                                    Please see in Chapter 2 of Electrical installation solutions for buildings - Technical details.


                                    4-pole RCBO from the ABB SMISSLINE protective devices range
                                    The combination of circuit protection and a residual current protection in one device as 4-pole
                                    RCBO simplifies both – planning and installation. It enables you to provide perfect protection
                                    in one device. This protection consists of:
                                    •  Short circuit protection
                                    •  Overload protection
                                    •  Residual current protection
                                    •  Preventive fire protection

                                    High rated short-circuit breaking capacity of 10 kA,  conforming to EN 61009-1
                                    The I  10 kA short-circuit breaking capacity of the RCBO complies with standard EN 61009-1.
                                        cn
                                    This standard specifies testing and usage of RCBO’s for household and similar uses.
                                    The devices can also be used by non-professionals.
                                    Features and benefits of the new devices:
                                    •  Overall width of 72 mm (4 modules)
                                    •  Rated sensitivity 30 mA
                                    •  Current rating 10 A to 32 A
                                    •  B and C tripping characteristics
                                    •  Easy Drive double deck terminals on the output side for connecting two conductors in one cham-
                                     ber. The two chambers can accommodate conductors with different cross sections.