9/40             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          SMISSLINE TP plug-in system
          Approvals according to IEC/EN 61439-6. Busbar system 125 A.




          Busbar system touch proof:
          Use only for wall mounted application (horizontal or vertical).
          When installed correctly the requirements of EN/IEC 61439-2 are met.
          Number of poles                                     max. 6 to 110
                                                              3p+N / 2 additional bars PE+N
          Rated operational voltage (U )                      690 V AC, 1000 V DC
                              e
                                                              (400 V AC, 250 V DC when used for load-free snap on and off under power)
          Rated insulation voltage (U )                       690 V AC, 1000 V DC
                            i
          IP Code                                             IP20B
          Mounting position                                   horizontal or vertical, direct mounting or mounting on DIN rail
                                                              acc. to EN 60715 35 mm
          Pollution degree                                    3 (690 V AC) 2 (1000 V DC)
          Rated impulse voltage (U  )                          8 kV (L1L2L3N)
                           imp
          Rated current of the assembly (I A)                 Max. 125 A side feeding
                                n
                                                              Max. 200 A (center feeding)
                                                              Max. 250 A (Double feed side or center)
          Auxiliary circuit                                   max. 40 A
          Rated current of a circuit (I )                     Main circuit: Max. 125 A
  9
                            nc
          Rated current of Auxiliary circuit                  40 A
          Rated short-time withstand current (I )             10 kA / 300 ms
                                    cw
          Auxiliary circuit                                   4 kA / 50 ms
          Rated peak withstand current (I )                   Main circuit: 30 kA
                                pk
          Auxiliary circuit                                   6 kA
          Rated frequency (f)                                 50/60 Hz
          Rated conditional short-circuit current (I )        100 kA (415 V, 50 kA)
                                      cc
          Ambient air temperature                             max. 60°C
                                                                          2
          Size of CU bars 3P+N+PE                             3 x10 mm (30 mm )
          Size of CU auxiliary bars La Lb                     2 x 5 mm (10 mm )
                                                                         2
          Rated conditional short-circuit    Incoming current of main busbars    Short circuit protection device
          current (I )           (L1, L2, L3, N)              (SCPD)
                cc
                                                              Fuse                       MCCB
                                                                                         ABB
                                 250 A
                                                                                         T   250 A
                                                                                          max
                                                              NH1 gG                     ABB
                                 200 A
                                                              690 V/200 A                T max  250 A
                                                              NH1 gG                     ABB
                                 160 A
          50 kA (690 V)                                       690 V/160 A                T   250 A
                                                                                          max
                                                                                         ABB
                                                              NH00 gG
                                 63 A                                                    Type S803S in combination with
                                                              690 V/63 A
                                                                                         Type S803S-SCL63-SR
                                 Incoming current
                                 of auxiliary busbars (LA LB)
                                                              NH00 gG                    ABB
          50 kA (415 V)          40 A
                                                              690 V/40 A                 Type S800 with 240 V/415 V
          Rated Voltage (U )   Rated conditional    Incoming current of main   Short circuit protection device
                      e
                               short-circuit current (I )  busbars (L1, L2, L3, N)  (SCPD)
                                               cc
                                                                       Fuse                 MCCB
          415 V                100 kA             250 A                NH1 gG 690 V/250 A   ABB
                                                                                            T   T4/XT4 250 A
                                                                                             max
          690 V                25 kA              250 A                NH1 gG 690 V/250 A   ABB
                                                                                            T max  T4/XT4 250 A
                                                  Incoming current
                                                  of auxiliary busbars (La Lb)
                               25 kA              40 A                 NH00 gG 415 V/40 A   ABB
                                                                                            Type S800 with
                                                                                            (240 V/415 V AC)