Page 871 - Din prodcuts 2020
P. 871

9/41




          —
          SMISSLINE TP plug-in system
          Busbar system 125 A




          SMISSLINE TP system for UL 508 – Industrial Control Equipment,
          CSA C22.2 No. 14 – Industrial Control Equipment UL File E222110

          Technical data UL508 Industrial Control Equipment SMISSLINE TP busbar system
          Rated Voltage: 600 V AC
          Rated Current (End feed, left and right): 125 A left, 125 A right
          Rated Current (Center Feed): 250 A max. if used with two feeder blocks.
          Short Circuit Ratings: 50 kA, max. 480 V AC and 480 Y/277 V and 240 V AC or 30kA, max. 600 V AC and 600 Y/347 V



          Technical data UL508 Industrial Control Equipment (ZLS906, ZLS908, ZLS920, ZLS926, ZLS928)
                       Busbar    Feeder     Feeder block   Combimodule   Universal-  Terminals   Combi modul  Adapter moter
                       ZLS200    ZLS924     ZLS95X     ZLS840X, 842X  adpter    ZLS95XUL,   ZMS132X  strater ZMS93X
                                                                   ZLS97X     91XUL
          Maximum      600 V AC  600 V AC   600 V AC   600 V AC    600 V AC   600 V AC  600 V AC   600  V AC
          rated voltage
          Maximum      125 A     150 A      150A       30 A        32 A, 63 A  32 A, 100 A,   32 A  32 A               9
          rated current                                                       150 A


          Terminals for 125A SMISSLINE TP System
          ZLS954UL - Terminal 150A (Neutral)
          ZLS959UL - Terminal (PE)
          ZLS918UL – Terminal 32A (Neutral)
          ZLS919UL - Terminal (PE)
          ZLS929UL - Terminal (PE)


          Circuit breaker accessories UL489 universal adapter
                       970UL, 971UL, 972UL or 973UL
          Maximum      600 V
           nominal voltage
          Maximum      25 A, 45 A
            nominal current
   866   867   868   869   870   871   872   873   874   875   876