SMISSLINE TP plug-in system
Technical data according to IEC/EN 61439-6
Power Bar System 250 A
Busbar system touch proof:
Use only for wall mounted application (horizontal or vertical).
When installed correctly the requirements of EN/IEC 61439-2 are met.
Number of poles: 6 to 110
3p+N / 2 additional bars PE+N
Rated operational voltage (U ): 690 VAC, 1000 VDC
e
(400 VAC, 250 VDC when used for load-free snap on and off under power)
Rated insulation voltage (U ) Main circuit: 690 VAC, 1000 VDC
i
Rated insulation voltage (U ) Auxilary circuit: 415 VAC
i
IP Code: IP20B
Mounting position: horizontal or vertical, direct mounting or mounting on DIN rail
acc. to EN 60715 35 mm
Pollution degree: 3 (690 V a.c.) 2 (1000 V d.c.)
Rated impulse voltage (U imp ): 8 kV Main circuit; 6 KV Auxiliary circuit
Rated current of the assembly (I A) : max. 250 A side feeding
n
Rated current of a circuit (I ) : Main circuit: Max. 100 A
nc
Rated current of Auxiliary circuit: 40 A 9
Rated short-time withstand current (I ): 15kA/100 ms Main circuit
cw
4 kA / 50 ms Auxiliary circuit
Rated peak withstand current Main circuit (I ): Main circuit: 30 kA
pk
Rated peak withstand current Auxilary circuit (I ): 6 kA
pk
Rated frequency (f): 50/60 Hz
Rated conditional short-circuit current (I ): see table below
cc
Ambient air temperature: max. 60°C
2
Size of CU bars 3P+N+PE: 3 x25 mm (75 mm )
2
Size of CU auxiliary bars La Lb: 2 x 5 mm (10 mm )
Rated Voltage (U ) Rated conditional Incoming current of main Short circuit protection device
e
short-circuit current (I ) busbars (L1, L2, L3, N) (SCPD)
cc
Fuse MCCB
415 V 100 kA 250 A NH1 gG 690 V/250 A ABB
T max T4/XT4 250 A
690 V 25 kA 250 A NH1 gG 690 V/250 A ABB
T max T4/XT4 250 A
Incoming current
of auxiliary busbars (La Lb)
25 kA 40 A NH00 gG 415 V/40 A ABB Type S800(240/415VAC)