9/62             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          SMISSLINE TP plug-in system
          Busbar system 250 A




          Technical data data UL508; Approvals for US and CA: cULus
          SMISSLINE TP system for UL 508 – Industrial Control Equipment,
          CSA C22.2 No. 14 – Industrial Control Equipment UL File E222110

          Technical data UL508 Industrial Control Equipment SMISSLINE TP busbar system
          Rated Voltage: 600 V AC
          Rated Current (End feed, left and right): 250 A left or right
          Short Circuit Ratings: 50 kA, max. 480 V AC, 480 Y/277 V and 240 V AC, or 30kA, max. 600 V AC and 600 Y/347 V



          Technical data UL508 Industrial Control Equipment (ZLSP906, ZLSP908, ZLSP920)
                       Busbar    Feeder     Feeder block   Combimodule   Universal-  Terminals   Combi modul  Adapter moter
                       ZLSP200   ZLS934     ZLS924, 95X  ZLS840X, 842X  adpter    ZLS95XUL,   ZMS132X  strater ZMS93X
                                                                   ZLS97X     91XUL
          Maximum      600 V AC  600 V AC   600 V AC   600 V AC    600 V AC   600 V AC  600 V AC   600  V AC
          rated voltage
          Maximum      250 A     250 A      150A       30 A        32 A, 63 A  32 A, 100 A,   32 A  32 A
  9
          rated current                                                       150 A



          Circuit breaker accessories UL489 universal adapter
                       970UL, 971UL, 972UL or 973UL
          Maximum      600 V
           nominal voltage
          Maximum      25 A, 45 A
            nominal current