Page 91 - Din prodcuts 2020
P. 91

1/81       1




          —
          MCBs
          SU 200 M series technical characteristic




                                     General Data
                                     Standards                         UL 489, CSA 22.2 No. 5, IEC/EN 60947-2
                                     Poles                             1P, 2P, 3P, 4P
                                     Tripping characteristics          C, K, Z
                                     Rated current In                  0.2 - 63 A
                                     Rated frequency f                 50 / 60 Hz, DC (0 Hz)
                                     Rated insulation voltage Ui acc. to IEC/EN   440 V AC (phase to phase)
                                     60664-1
                                     Overvoltage category              III
                                     Pollution degree                  3
                                     IEC/EN 60947-2
                                     Rated operational voltage Ue      1P: 230 V AC; 2P, 3P, 4P: 400 V AC
                                     Max. power frequency recovery voltage Umax AC  1P: 253 V AC; 2P, 3P, 4P: 440 V AC
                                     Min. operating voltage            12 V AC, 12 V DC
                                     Rated ultimate short-circuit breaking capacity   15 kA
                                     Icu
                                     Rated service short-circuit breaking capacity Ics   ≤ 40 A: 11.25 kA
                                                                       > 40 A: 7.5 kA
                                     Rated impulse withstand voltage Uimp   4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
                                     (1.2/50μs)
                                     Dielectric test voltage           2 kV (50 / 60Hz, 1 min.)
                                     Reference temperature for tripping   30 °C
                                     characteristics
                                     Electrical endurance              In < 30 A: 20,000 ops (AC), In ≥ 30 A: 10,000 ops. (AC);
                                                                       1 cycle (2 s - ON, 13 s - OFF, In ≤ 32 A), 1 cycle (2 s - ON,
                                                                       28 s - OFF, In > 32 A)
                                     UL / CSA
                                     Rated voltage                AC   1P: 277 V AC up to 40 A for C, Z char.,
                                                                  AC   277 V AC up to 35 A for K char., 240 V AC
                                                                  AC   2P, 3P, 4P: 480 Y / 277 V AC up to 40 A for C, Z char.,
                                                                  AC   480 Y / 277 V AC up to 35 A for K char., 240 V AC
                                                                  DC   1P: 48 V DC; 2P: 96 V DC (2p in series)
                                     Rated interrupting capacity acc. to UL 1077   –
                                     Short-circuit current rating acc. to UL 489   10 kA
                                     Application                       –
                                     Reference temperature for tripping   40 °C
                                     characteristics
                                     Electrical endurance              6,000 ops (AC), 6,000 ops. (DC); 1 cycle (1 s - ON, 9 s - OFF)
   86   87   88   89   90   91   92   93   94   95   96