Page 92 - Din prodcuts 2020
P. 92
1/82 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
1
—
MCBs
SU 200 M series technical characteristic
Mechanical data
Housing Insulation group II, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (green OFF / red ON)
Protection degree acc. to DIN EN 60529 IP20*, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5g - 20 cycles at 5…150…5 Hz with load 0.8 In
Environmental conditions (damp heat cyclic) 28 cycles with 55°C/90-96% and 25°C/95-100%
acc. to IEC/EN 60068-2-30
Ambient temperature -25 … +55°C
Storage temperature -40 ... +70 °C
Installation
Terminal Failsafe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) solid, stranded: 35 mm² / 35 mm²
flexible: 25 mm / 25 mm 2
2
18 – 4 AWG
Cross-section of busbars (top/bottom) 10 mm² / 10 mm²
18 – 8 AWG
Torque 2.8 Nm
AWG 18-16: 13.3 in-lbs.
AWG 14-10: 17.7 in-lbs.
AWG 8-4: 39.8 in-lbs.
Screwdriver No. 2 Pozidrive
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply optional
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 3
Pole dimensions (H x D x W) 111 x 69 x 17.5 mm
Pole weight approx. 125 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal contact Yes
Shunt trip Yes
* Also fulfilling the requirements acc. to the protection degree IPXXB