80               SAFETY SWITCHES AND ENCLOSED SWITCH-DISCONNECTORS SAFE AND DEPENDABLE PERFORMANCE




          —
          Technical data
          Enclosed switch-disconnectors







          —
          Enclosed switch-disconnectors, types BW, KSE and KSF
          Technical data according to IEC60529 and IEC 60947-3
                                                                        BW       BW       BW
                                                                       KSE      KSE       KSE
                                                              BW       KSF      KSF       KSF      KSE       KSE
          Type/size                                           _16      _25       240      _40       _63      _80
          Rated insulation voltage                    V       690      690       690      690      750       750
          Rated thermal current and rated     40ºC    A        16       25       40        40       63       80
          operational current AC20/DC20       60ºC    A                                             50        63
          Rated operational current,          400V    A        16       25       40        40       63       80
          AC-21A and AC-22A                   500V    A        16       25       40        40       63       80
                                              690V    A        16       16        32       32       63       80
          Rated operational current,      up to 415 V  A       16       16        32       25       45        75
          AC-23A                              440V    A        16       16        25       25       45        65
                                              500V    A        10       16        25       25       45        58
                                              690V    A        10       10        16       16       20        20
          Rated conditional short-circuit  25kA, 500V  kA     4.8       4.8      4.8      4.8
          current r.m.s and corresponding
          cut-off current of the fuse in sing-  50kA, 415V  kA  50/50  50/50   50/50    50/50
          le-phase test according to IEC60269
                                      Fuse size: gG/aM  A
          Rated frequency                             Hz    50/60     50/60    50/60    50/60     50/60    50/60
          Cu-wire size suitable for terminal        mm 2      1-10     1-10     1-10      1-10    1.5-35   1.5-35
          Terminal bolt size

          —
          Enclosed switch-disconnectors, ONE20_
          Technical data according to IEC 60947-3
          Data according to IEC 60947-3                                          ONE20M2_    ONE20M3_    ONE20M4_
          Impulse withstand voltage, Uimp                                kV           6           6           6
          Operating temperature                                                 -30°C...+60°C  -30°C...+60°C  -30°C...+60°C
          Rated operational voltage, Ue                                   V          240         415         415
          Rated insulation voltage                         Pollution degree 3  V     690         690         690
          Rated thermal current and rated operational current AC20/DC20  Ambient 40°C  A  20      20          20
          Rated operational current, AC-21A and AC-22A            240V    A          20           20          20
                                                               up to 415V  A                      20          20
          Rated operational current , AC-23A                      230V  A/kW       15.2/2.6    15.2/2.6    15.2/2.6
                                                              up to 400V  A/kW                 15.2/7.5    15.2/7.5
          Rated operational current and power, AC-3A              230V  A/kW       11.3/2.2    11.3/2.2    11.3/2.2
                                                              up to 400V  A/kW                 11.3/5.5    11.3/5.5
          Rated operational short circuit current, lp(rms), with fuses   kA           1           1            1
          Maximum back-up fuse link                                       A          20           20          20
          Cu-wire size suitable for terminal                            mm 2        0.5-4       0.5-4       0.5-4
          Cable for compression glands, min-max diameter                 mm          7-12        7-12        7-12