Page 116 - Ferraz semiconductor DIN
P. 116

Protistor   ®
                                                                              Semiconductor (AC) fuses

            Times/Current Characteristics size 1
        Protistor ®  Square-body Fuses: NH Plain Blades gS
                       160A    250A
                     125A 200A  280A
                 7000                                 a=130       Cut off characteristics - Peak let thru
                 5000                                A 2 =0.75
                                                                  current - size 1
                 3000                                B 1 =1.25
                 2000                         B 2 =0.80 for tp>100s
                                                                   70000
                                             B 2 =0.75 for 100≥tp≥5s  50000                                    280 A
                 1000                                                                        Im = 2.3 Ip
                  700                           B 2 =0.60 for 5s>tp  30000                                     250 A
                  500                                Cf 3 =0.80    20000                                       200 A
                  300                                                                                          160 A
                  200                                              10000                                       125 A
                  100                                               7000
                                                                    5000
                   70
                   50                                              Maximum peak let thru current (Im)(A)  3000
                                                                    2000
              Actual prearcing time (s)  10 7 5 3 2                 1000
                   30
                   20
                                                                     700
                                                                     500
                                                                     300
                                                                     200
                   0.7 1                                                   200  300  500  700  1000  2000  3000  5000  7000  10000  20000  30000  50000  70000  100000  200000  300000
                   0.5
                                                                                     50 Hz RMS Symetrical prospective current (Ip)(A)
                   0.3
                   0.2
                   0.1
                  0.07
                  0.05                                            Peak arc voltage vs applied AC voltage size 1
                  0.03
                  0.02
                  0.01                                              1600
                 0.007
                 0.005                                              1500
                 0.003                                              1400
                 0.002
                 0.001
                0.0007                                              1200
                0.0005                                             Peak arc voltage (V) 1300
                0.0003                                              1100
                0.0002                                              1000
                                                                     900
                        200  300  500  700  1000  2000  3000  5000  7000  800
                                       RMS value of prearc current (A)  700

                                                                     600

            Clearing I²t and arcing time correction                      100   200   300   400   500  600   700
            factor vs Applied AC voltage size 1                                                       Applied AC voltage (V)

                1.3
                1.2
                                                                  Watts loss vs % rated current size 1
                1.1 1
              Clearing I 2 t and arcing time correction factor  0.8    Correction Factor for Watts Loss  0.8
                0.9

                0.7
                                                                        0.6
                0.6
                0.5
                0.4
                0.3
                0.2                                                     0.4
                                                                        0.2
                0.1
                   100  200  300  400   500  600  700                       50   60    70   80    90
                                             Applied AC voltage (V)                            % rated current



      5
   111   112   113   114   115   116   117   118   119   120   121