Page 118 - Ferraz semiconductor DIN
P. 118

Protistor   ®
                                                                              Semiconductor (AC) fuses

            Times/Current Characteristics size 3
        Protistor ®  Square-body Fuses: NH Plain Blades gS
                     350A
                              450A
                        400A
                   315A         500A
                                 550A
               7000                                        a=130  Cut off characteristics - Peak let thru
               5000               630A                    A 2 =0.75
                                                                  current - size 3
               3000                                       B 1 =1.25
               2000                                B 2 =0.80 for tp>100s
                                                                    70000
                                                  B 2 =0.75 for 100≥tp≥5s                                      630 A
               1000                                                 50000                      Im = 2.3 Ip
                700                                 B 2 =0.60 for 5s>tp  30000                                 550 A
                500                                       Cf 3 =0.80  20000
                300                                                                                            500 A
                200                                                 10000                                      450 A
                100                                                 7000                                       400 A
                                                                    5000
                 70                                                Maximum peak let thru current (Im)(A)
                 50                                                 3000                                       350 A
                                                                    2000
                 30
              Actual prearcing time (s)  10 7 5 3 2                 1000
                                                                                                               315 A
                 20
                                                                     700
                                                                     500
                                                                     300
                                                                     200
                0.7 1                                                      200  300  500  700  1000  2000  3000  5000  7000
                0.5                                                                           10000  20000  30000  50000  70000  100000  200000
                0.3                                                                  50 Hz RMS Symetrical prospective current (Ip)(A)
                0.2
                0.1
               0.07
               0.05
                                                                  Peak arc voltage vs applied AC voltage size 3
               0.03
               0.02
               0.01                                                 1600
              0.007
              0.005                                                 1500
              0.003
                                                                    1400
              0.002
                                                                   Peak arc voltage (V) 1300
              0.001
             0.0007                                                 1200
             0.0005
             0.0003                                                 1100
             0.0002                                                 1000

                   300  500  700  1000  2000  3000  5000  7000  10000  20000  30000  50000  900
                                                                    800
                                            RMS value of prearc current (A)
                                                                    700
                                                                    600

            Clearing I²t and arcing time correction                      100   200   300   400   500   600    700
            factor vs Applied AC voltage size 3                                                        Applied AC voltage (V

               1.3
               1.2
                                                                Watts loss vs % rated current size 3
               1.1 1
              Clearing I 2 t and arcing time correction factor  0.8  Correction Factor for Watts Loss 0.8
               0.9

               0.7
                                                                      0.6
               0.6
               0.5
               0.4
               0.3
               0.2                                                    0.4
                                                                      0.2
               0.1
                   100  200  300  400   500  600  700
                                             Applied AC voltage (V)       50    60    70   80    90
                                                                                               % rated current

      7
   113   114   115   116   117   118   119   120   121   122   123