Page 195 - Ferraz semiconductor DIN
P. 195

Semiconductor fuses
       Semiconductor (AC) fuses


       Protistor Square-body Fuses
                     ®
       PSC aR sizes 7x - 650 V to 1300 VAC
       Curves set





                                                               Time-current characteristics
       Size 72

       Cut-off characteristics
       Below, right: Curves indicating for each rated
       current the peak value I that the current may
                              c
       reach as a function of the prospective fault
       current I .
               p

































       Time-current characteristics

       Above, left: Curves indicating pre-arcing time for             Size
       each rated current as a function of RMS value of pre-           72
       arcing current I.
       - Tolerances on this current ± 8 %.
       - Beyond 30 sec, small overloads must be eliminated
        by another device.
       - Curve CC’ represents the maximum times taken by the
        associated device to clear small overloads; only its
        horizontal line is
        represented. Its oblique line must be plotted accord-
        ing to  sketch, top right corner.
       - The intersection of the fuse and CC’ curves indicates
        the minimum breaking current I pm  of the fuse.

       Maximum values of total operating
       I t and total operating times
        2
       Left:  Horizontal curves indicating the maximum
                                  2
                               2
       values of total operating I t (I t ) as function of the
                                   t
       prospective current I at 1000V or 850 V(*),
                          p
       cos ϕ = 0.15.
       The oblique lines indicate the corresponding total
       operating time T , with pre-arcing time in brackets.
                       t
                                                          SCAC137
       12/04
   190   191   192   193   194   195   196   197   198   199   200