Page 198 - Ferraz semiconductor DIN
P. 198
Semiconductor fuses
Semiconductor (AC) fuses
®
Protistor Square-body Fuses
PSC aR sizes 7x - 650 V to 1300 VAC
Curves set
Size 2x72
Cut-off characteristics
Time-current characteristics
Curves indicating for each rated
current the peak value I that the current may
c
reach as a function of the prospective fault
current I .
p
Time-current characteristics
Curves indicating pre-arcing time for each rated current
as a function of RMS value of pre-arcing current I. Size
- Tolerances on this current ± 8 %. 2x73
- Beyond 30 sec, small overloads must be eliminated by
another device.
- Curve CC’ represents the maximum times taken by the
associated device to clear small overloads; only its
horizontal line is represented. Its oblique line must be
plotted according to sketch, top right corner.
- The intersection of the fuse and CC’ curves indicates
the minimum breaking current I pm of the fuse.
2
Maximum values of total operating I t
and total operating times
Horizontal curves indicating the maximum values of
total operating I t (I t ) as function of the prospective
2
2
t
current I at 1000V or 850 V(*), cos ϕ = 0.15.
p
The oblique lines indicate the corresponding total
operating time T , with pre-arcing time in brackets.
t
SCAC140 12/04