Page 318 - Ferraz semiconductor DIN
P. 318

Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                                                      ®
                                                                            Other Protistor Fuses
                                                                                           Ferrule Fuses
                                              10x38 URB/URD/URL - 500 to 600 VAC






                                              Extremely high breaking capacity fuses:
                                              Protection of power semiconductors complying with IEC standard
                                              60269.1 and 4.

                                              500 - 600 VAC voltage rating

                                              aR-CLASS according to VDE 636-23 IEC 60269-4


                                              Without blown fuse indication 0.10 up to 0,80 A**

                                              With trip-indicator (1 to 30 A), a Ferraz Shawmut speciality*





            Main Characteristics


                                                                       2
               Voltage                 Current   Pre-arcing  Total clearing I t @ U N  Watts loss       Tested
                                                                     2
                                                                 2
                                                 2
                rating      Class      rating    I t @ 1 ms      I tt (A s)      0.8 I N    I N    breaking capacity
                                                      2
                                                  2
              U ( VAC )                I ( A )   I tp (A s)
                                       N
                N
                                       100 mA                    1.2 10 -3         0.23    0.4
                                       125 mA                    2.3 10 -3         0.25    0.44
                                       160 mA                    5.2 10 -3         0.28    0.48
                600 V                  200 mA                    8    10 -3        0.34    0.58
               without      URD        250 mA                   18    10 -3        0.35    0.60         200 kA
              blown fuse               315 mA                   33    10 -3        0.42    0.73        @ 600 V
               indicator     **        400 mA                   56    10 -3        0.46    0.80
                                       500 mA                    0.100             0.46    0.80
                                       630 mA                    0.18              0.52    0.90
                                       800 mA                    0.44              0.58    1
                                        1 A        0.40          3.6               2.8     0.5
                            URD
                                        1.25 A     0.13          1.7               0.52    0.91
                                        1.6 A      0.31          2.2               0.58    1
                                        2 A        0.65          3.1               0.63    1.1          50 kA
                                        2.5 A      1.65          5.9               0.63    1.1         @ 500 V
                                        3.15 A     2.80           9                0.86    1.5
                                        4 A        5.30         16                 1.1     1.8
                500 V                                                                      1.8
                 with                   5 A       12.7          36                 1.1
             trip-indicator             6 A        1.3          47                 0.73    1.35
                                        8 A        2.3          80                 0.,83   1.55
                            URD         10 A       3.6          110                1       1.9          50 kA
                                        12 A       5.25         150                1.3     2.3         @ 500 V
                                        16 A       9.30         200                1.7     3.1
                                        20 A      16            290                1.7     3.2
                             URL        25 A      37            580                2.9     4.25         50 kA
                                        30 A      58            900                3.5     5.1         @ 500 V
             * minimum operating voltage for trip-indicator: 20 V
             ** higher ratings without blown fuse indicator see 10x38gRB - 690 VAC















                                                          SCAC170                                              12/04