Page 321 - Ferraz semiconductor DIN
P. 321

Semiconductor fuses
       Semiconductor (AC) fuses


                                 ®
       Other Protistor Fuses
       Ferrule Fuses
       10x38 URB/URD - 500 to 600 VAC






        Corrective factor - Peak arc voltage



       Corrective factor                                                 Peak arc voltage



         K                     600 V UR
                               1 : 0.1 up to 0.8 A
         1

        0,6                       These mean curves show
           1
                                  the variation of the
        0,2                                           2
                                  total clearing time (I t )
                                                       t
             200  400  600  U(V)  and the total clearing
                                  duration t as a function
                                           t
                                  of operating voltage U.
          K
                               500 V UR
         1,2                   1 : 1 up to 5 A
         1                     2 : 6 up to 30 A
         0,8
         0,6
           1                                                       This curve shows the peak value Um of
         0,4
         0,2  2                                                    the arc voltage which appears across the
                                                                   fuse link as a function of the operating
            100  300  500  U(V)
                                                                   voltage U @ cos ϕ = 0.15.


         D.C. Application data for fuses with trip indicator





                         500 V URD IN ≥ 6A                                    500 V URD IN ≥ 6A

          L
           (ms)
          R
            80
            70
            60
            50
            40
            30
            20

            10
             0                                                    This curve shows the peak value Um of
                  100  200 300  400  500 600 U(V)                 the arc voltage which appears across the
                                                                  fuse link as a function of the operating
                                                                  voltage U.





                                                          SCAC173
       12/04
   316   317   318   319   320   321   322   323   324   325   326