Page 334 - Ferraz semiconductor DIN
P. 334

Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                            Other Protistor Fuses
                                                                                                      ®
                                                                                           Ferrule Fuses
                             14x51 URGB & 22x58 URGA - 600 V to 690 VAC






                                                      EXTREMELY HIGH BREAKING CAPACITY FUSES:
                                                      PROTECTION OF POWER SEMICONDUCTORS AS PER
                                                      IEC STANDARD 60269.1 AND 4



                                                      600 V - 690 V AC VOLTAGE RATING



                                                      aR CLASS AS PER VDE 636-23 AND IEC 60269.4



                                                      WITH AND WITHOUT TRIP-INDICATOR
                                                      FOR SIZES 14 x 51 AND 22 x 58











             Main Characteristics


              Voltage                    Current  Pre-arcing  Total clearing I t @ A s
                                                                             2
                                                                        2
                                                   2
               rating   Size    Class    rating   I t @ 1 ms                          Watts loss         Tested
                                                        2
                                                   2
             U ( VAC )                   I N  (A)  I tp (A s)      660 V                             Breaking capacity
              N                                                                   0,8 I       I
                                                              Ip ≤ 30 I N  Ip > 30 I N  N     N
                                            8         3.3        20        17       1.45      2.7
                                           10         6.0        37        30       1.85      3.4
                                           12         9.3        75        60       2.5       4.6
                                           16        15.6        95        75       3.4       6.2
                       14 x 51  URGB       20        30.0       175       145       4         7.4        200 kA
                                           25        53.5       300       250       4.7       8.6       @ 690 V
                                           32       100         550       460       5.7      10.6
                                           40       214       1150        940       6.2      11.5
               690 V                       50       480       2550       2070       7        13
                                           25        45              210            4.7       8.5
                                           32        84              400            5.7      10.3
                                           40       150              700            7.1      12.8
                                           50       270            1270             8.7      15.7
                                           63       595            2770             9.8      17.7
                       22 x 58  URGA
                                           80      1165            5500            12        21.7        200 kA
                                                                                   14.2      25.6       @ 690 V
             600* - 690 V  22 x 58  URGA  100*     2150             9000*         14.2       25.6    200 kA @600 V

                                                                                                  2
                                                                                   2
             *Operating voltage limited to 600 V for the model with blown fuse trip-indicator / Total clearing I t @ 600 V = 9000 A s
             Minimum operating voltage for built-in trip-indicator: 20 V