CLASS L POWER FUSES





          PUT THE HIGHEST
          CURRENT-LIMITATION . . .
          AT YOUR SERVICE.
          Amp-trap 2000® A4BQ fuses are 20% more current limiting than any other Class L fuse on the market.
          When correctly coordinated, they bring a superior level of protection to service entrance equipment.
          Downstream circuit components have maximum protection against short circuit let-thru current. A4BQ’s
          built-in, 4-second time delay characteristic (at 500% of rated current) accommodates harmless inrush
          currents with no nuisance opening.
          Features / Benefits
          Fastest operation under short circuit conditions: Let-thru currents are typically 20% lower with a
                                      2
          corresponding let-thru energy (clearing l t) up to 40% lower than the next fastest Class L fuse.
          Time delay for high inrush loads such as motors and transformers, without nuisance opening.
          300kA interrupting rating - self-certified, UL witnessed tests.
          Most current limiting for lowest peak letthru current; even at fault currents up to 300kA.
          Pure silver links ensure lowest let-thru current and longer fuse life.
          Easy 2-to-1 selectivity for prevention of nuisance shutdowns and “blackouts:
          Rejection-style design prevents replacements errors.
          High-visibility orange label gives instant recognition.
          Reduced inventory because A4BQ can replace all older types of Class L fuses now in service.
          Metal-embossed date and ref number for traceability and lasting identification.
          Fibreglass body provides dimensional stability in harsh industrial settings
          High-grade silica filler ensures fast arc qenching.




          Ratings
          AC: 100 to 6000A
          600VAC, 200kA I.R. (self certified for 600VAC, 300kA I.R., UL witnessed)
          4-second delay at 500% rating
          Note: 100-600A ratings are non-listed
          DC: 601 to 3000A
          500VDC, 100kA I.R.


                           Highlights:                       Applications:
                                                             Mains, Feeders
                           Time Delay
                                                             Large Motors
                           Industry’s Most
                                                             Lighting, Heating & General Loads
                           Current-Limiting                  Circuit Breaker Back-up
                           Class L Fuse                      DC Rate: UPS DC Links, Battery Disconnects, Other DC Applications
                           Pure Silver Elements
                                                             Approvals:
                           AC & DC Rated
                                                             UL Listed to Standard
                                                             248-10 (601-6000A)
                                                             DC Listed to UL Standard
                                                             198L (601-3000A)
                Safety Note: Class L fuses are dimensioned for
                                                             CSA Certified to Standard C22.2 No.
                one-way interchangeability. A Class L fuse of any
                                                             248.10 (601-6000A)
                lower ampere rating can be substituted for a give
                                                             IEC 269-2-1
                Class L fuse.
                *Note UL Listed or CSA Certified




                            IPD INDUSTRIAL PRODUCTS            Phone: 1300 556 601            www.ipdgroup.com.au
                                                                                                                  25