Page 161 - General_Purpose_Enclosures _Aria, APO,Polysafe
P. 161
161
—
Power dissipation values
ARIA
Frontside and upperside free Temperature rise [Kelvin]
Dissipa- ARIA 32 ARIA 43 ARIA 54 ARIA 64 ARIA 75 ARIA 86 ARIA 108
tion 300×200×170 400×300×170 500×400×230 600×400×230 700×500×270 800×600×300 1.000×800×300
Watt Half Top Half Top Half Top Half Top Half Top Half Top Half Top
10 14 17 9 11 6 8 6 7 4 5 4 5 3 3
20 24 30 16 20 11 14 10 12 8 9 7 8 4 6
30 33 41 23 28 16 19 14 17 11 13 9 11 6 8
40 42 52 29 35 20 24 17 22 13 16 11 14 8 10
50 34 42 23 29 21 26 16 20 14 17 9 12
60 40 48 27 33 24 30 18 23 16 19 11 14
70 45 55 31 37 27 34 21 26 18 22 12 16
80 34 42 31 38 23 29 20 24 14 18
90 38 46 34 41 26 31 22 27 15 19
100 41 50 36 45 28 34 24 29 16 21
110 39 49 30 37 26 31 18 23
120 42 52 32 40 27 34 19 24
130 34 42 29 36 20 26
140 37 45 31 38 21 27
150 39 47 33 40 23 29
160 41 50 35 42 24 31
170 36 44 25 32
180 38 47 26 34
190 40 49 27 35
200 41 51 29 37
210 30 38
220 31 40
230 32 41
240 33 42
250 34 44
260 35 45
270 36 47
280 37 48
290 39 49
300 40 51
310
320
330
340
Frontside free, upper side not free Temperature rise [Kelvin]
Dissipa- ARIA 32 ARIA 43 ARIA 54 ARIA 64 ARIA 75 ARIA 86 ARIA 108
tion 300×200×170 400×300×170 500×400×230 600×400×230 700×500×270 800×600×300 1.000×800×300
Watt Half Top Half Top Half Top Half Top Half Top Half Top Half Top
20 27 33 19 23 12 15 11 14 8 10 7 8 5 6
30 37 46 26 32 17 21 15 19 11 14 10 12 7 9
40 47 57 33 40 22 26 19 24 14 18 12 15 9 11
50 39 48 26 32 23 28 17 21 14 18 10 14
60 45 56 30 37 27 33 20 24 17 21 12 16
70 34 41 30 37 23 28 19 23 13 18
80 38 46 33 41 25 31 21 26 15 20
90 42 51 37 45 28 34 23 28 16 22
100 40 49 30 37 25 31 18 24
110 32 40 27 33 19 26
120 35 43 29 36 21 27
130 37 45 31 38 22 29
140 39 48 33 41 23 31
150 42 51 35 43 25 33
160 37 45 26 35
170 39 47 27 36
180 41 50 29 38
190 30 40
200 31 41
210 32 43
220 34 45
230 35 46
240 36 48
250 37 49
260 39 51
270
280
290
300
310
320
330
340