Page 164 - General_Purpose_Enclosures _Aria, APO,Polysafe
P. 164
164 GENER AL PURPOSE ENCLOSURES HE AV Y DUT Y AND INDUSTRIAL ENCLOSURES
—
Power dissipation values
PolySafe
Stand alone Temperature rise [Kelvin]
Dissipa- PS 220 PS 230 PS 320 PS 330 PS 340 PS 352 PS 420 PS 430 PS 440/442 PS 452 PS 530 PS 542/546
tion 500×500 500×750 750×500 750×750 750×1.000 750×1.250 1.000×500 1.000×750 1.000×1.000 1.000×1.250 1.250×750 1.250×1.000
Watt Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top
20 7 9 6 7 6 8 4 6 5 7
40 13 15 10 13 10 13 8 10 6 8 5 6 8 12 6 8 5 6 4 5 5 7
60 17 21 14 17 14 19 11 14 11 16 8 11
80 22 26 17 22 17 23 13 18 10 13 9 11 14 21 10 14 8 11 7 9 8 12 7 9
100 26 31 21 26 20 28 16 21 17 25 12 16
120 30 36 24 30 24 33 19 25 14 18 12 15 20 28 14 19 11 15 9 12 12 17 9 13
140 34 41 27 34 27 37 21 28 22 32 16 22
160 38 46 30 38 30 41 24 31 18 23 15 19 25 36 17 24 14 19 12 15 15 21 12 16
180 42 50 33 42 33 45 26 34 27 39 19 26
200 46 55 36 46 36 49 28 37 21 27 18 23 29 43 21 29 17 22 14 18 17 25 14 19
220 50 59 39 50 38 53 30 40 32 46 23 31
250 43 55 43 59 34 45 25 33 21 27 35 51 25 34 20 27 17 22 21 30 17 23
300 50 64 49 68 39 52 29 38 25 31 41 59 29 40 23 31 19 25 24 34 19 27
350 44 58 33 43 28 36 46 67 33 45 26 35 22 29 27 39 22 30
400 49 65 37 48 31 40 51 75 36 50 29 39 24 32 30 43 24 34
450 54 71 41 53 34 43 40 55 32 43 27 35 33 48 27 37
500 44 57 37 47 44 60 35 47 29 38 36 52 29 40
550 48 62 40 51 47 65 38 51 32 41 39 56 31 43
600 51 66 43 55 50 69 41 54 34 44 42 60 34 46
700 49 62 46 61 38 50 48 68 38 53
800 54 69 51 68 43 56 53 76 42 58
900 47 61 47 64
1.000 51 67 51 70