Page 43 - IDEC relay catalogue
P. 43

Relays & Sockets                                                                 RY/RM Series




         Specifications
                                                       Standard Contact                            Bifurcated Contact
             Contact Model
                                 RY2 - DPDT Slim       RM2 - DPDT Wide         RY4 - 4PDT       RY22 - DPDT / RY42 - 4PDT
         Contact Material   Gold-plated silver    Silver                Gold-plated silver     Silver-palladium alloy
         Contact Resistance  1  50 mΩ maximum     30 mΩ maximum         50 mΩ maximum          100 mΩ minimum          Switches & Pilot Lights
                            24V DC, 5 mA; 5V DC,   24V DC, 10 mA; 5V DC,   24V DC, 5 mA; 5V DC,
         Minimum Applicable Load                                                               1V DC, 100 μA (reference value)
                            10 mA (reference value)  20 mA (reference value)  10 mA (reference value)
         Operate Time  2                                           20 ms maximum
         Release Time  2                                           20 ms maximum
         Power Consumption   AC: 1.1 VA (50 Hz), 1 VA (60 Hz)  AC: 1.4 VA (50 Hz), 1.2 VA (60 Hz)  AC: 1.4 VA (50 Hz), 1.2 VA (60 Hz)  AC: 1.1 VA (50 Hz), 1 VA (60 Hz)
         (approx.)          DC: 0.8W              DC: 0.9W              DC: 0.9W               DC: 0.8W
         Insulation Resistance  100 MΩ minimum (500V DC megger)
                                                               Between live and dead parts:
                                1500V AC, 1 minute     2000V AC, 1 minute    2000V AC, 1 minute    1500V AC, 1 minute  3  Display Lights
                                                                Between contact and coil:
                                1500V AC, 1 minute     2000V AC, 1 minute    2000V AC, 1 minute    1500V AC, 1 minute
         Dielectric Strength  3
                                                             Between contacts of different poles:
                                1500V AC, 1 minute     2000V AC, 1 minute    2000V AC, 1 minute    1500V AC, 1 minute
                                                             Between contacts of the same pole:
                                1000V AC, 1 minute     1000V AC, 1 minute    1000V AC, 1 minute    1000V AC, 1 minute
                            Electrical:     1800 operations/h maximum
         Operating Frequency
                            Mechanical:    18,000 operations/h maximum                                                 Relays & Sockets
                            Damage limits:    10 to 55 Hz, amplitude 0.5 mm
         Vibration Resistance
                            Operating extremes:   10 to 55 Hz, amplitude 0.5 mm
                            Damage limits:   1000 m/s 2
         Shock Resistance
                                               2
                                                            2
                            Operating extremes:   100 m/s  (DPDT Slim), 200 m/s  (4PDT, DPDT Wide)
         Mechanical Life                                         50,000,000 operations
                                                                        100,000 operations (220V AC, 5A)
         Electrical Life    200,000 operations (220V AC, 3A)  500,000 operations (220V AC, 5A)  200,000 operations (110V AC, 1A)
                                                                        200,000 operations (220V AC, 3A)
         Operating Temperature  4  –25 to +55°C (no freezing)  –25 to +45°C (no freezing)  –25 to +55°C (no freezing)  5  –25 to +55°C (no freezing)
         Operating Humidity  45 to 85% RH (no condensation)
         Weight (approx.)            23g                   35g                    34g             RY22: 23g / RY42: 34g  Timers

             Note: Above values are initial values.   3.  Relays with indicator or diode: 1000V AC, 1 minute  5.   When the total current of 4 contacts
             1.  Measured using 5V DC, 1A voltage drop method  4.  For use under different temperature conditions, refer to   is less than 15A, the operating tempera-
             2.  Measured at the rated voltage (at 20°C), excluding contact bouncing  Continuous Load Current vs. Operating Temperature Curve.   ture range is –25 to +70°C.
                Release time of relays with diode: 40 ms maximum  The operating temperature range of relays with indicator or diode is –25 to +40°C.  Terminal Blocks