Page 58 - IDEC timer catalogue
P. 58
GT5P Series Timers
GT5P Series — ON Delay Timers
Switches & Pilot Lights • SPDT, 5A contacts
Key features of the GT5P series include:
•
8-pin, octal base
9 time ranges
•
Repeat error ±0.2% maximum
•
•
Power ON and timing out LED indicators
• Control settings by hand or screwdriver
• Uses the same sockets and hold down clips as IDEC’s RR2P 8-pin relays
UL Recognized CSA Certifi ed
File No. E55996 File No. LR66809
Display Lights Specifications
100 to 120V AC (50/60Hz)
200 to 240V AC (50/60Hz)
Rated Operating Voltage
24V AC/DC
12V DC
AC type: ±15%
Voltage Tolerance DC type: ±10%
(ripple 10% maximum)
Relays & Sockets Contact Rating Resistive load 120V AC/24V DC, 5A
240V AC, 3A
240V AC, 0.8A
Inductive load
120V AC, 1.4A
Allowable Contact Power 24V DC, 1.7A
960VA AC
(resistive load) 120W DC
Contact Form SPDT
Voltage 250V AC, 150V DC
Repeat Error ±0.2% ±10msec
Timers Voltage Error ±0.5% ±10msec
±3% maximum (over –10 to 50°C, reference temperature 20°C)
Temperature Error
Setting Error ±10% maximum
When turning power off after time up:
0.1 sec maximum
Reset Time
When turning power off before time up:
1 sec maximum
Insulation Resistance 100MΩ minimum
2000V AC, 1 minute (except between contacts of the same pole)
Dielectric Strength
Terminal Blocks Vibration Resistance 100N (approximate 10G)
Operating extremes:
100N (approximate 10G)
Shock Resistance
Damage limits: 500N (approximate 50G)
100V AC type: 1.5VA (at 50Hz)
Power Consumption 200V AC type: 1.6VA (at 50Hz)
24V DC type: 0.9W
Electrical Life 100,000 operations minimum (at rated load)
Mechanical Life 20,000,000 operations minimum
Circuit Breakers Operating Humidity 45 to 85% RH
–10 to +50°C
Operating Temperature
1. Inductive load (reference), cos ø =0.3 to 0.4 or L/R=15msec.
2. Minimum applicable load: 5VDC/10mA (reference).
848 www.idec.com