Page 54 - IDEC timer catalogue
P. 54

GE1A Series                                                                          Timers


                                                GE1A Series — ON Delay Timers

     Switches & Pilot Lights  Key features of the GE1A series include:
                                                      Single Function

            DPDT or SPDT + instantaneous SPDT
          •
          •
            8-pin, octal base
          •
            Repeat error ±0.2% maximum
          •
            Large, clear knob for easy setting
          •  8 time ranges
          •  Instant monitoring of operational status by LED indicators

     Display Lights                UL, c-UL Listed
                                   File No. E55996



         Specifications

                          24V AC/DC
         Rated Operating Voltage  100 to 120V AC
                          220 to 240V AC
                          AC: 85 to 110%
         Voltage Tolerance  DC: 90 to 110%
     Relays & Sockets  Contact Rating  240V AC/5A
                          24V DC/5A
                          DPDT or SPDT+ instantaneous SPDT
         Contact Form
         Repeat Error
                          ±0.5% ±10msec maximum
         Voltage Error    ±0.2% ±10msec maximum
         Temperature Error  ±3% maximum
         Setting Error    ±10% maximum
         Reset Time       0.1 sec maximum
         Insulation Resistance  100MΩ minimum (500V DC megger)
     Timers  Dielectric Strength  Between power and output terminals: 1,500V AC, 1 minute
                          Between contact circuits: 750V AC, 1 minute
                          Damage limits: Amplitude 0.75mm, 10 to 55 Hz
         Vibration Resistance
                          Operating extremes: Amplitude 0.5mm, 10 to 55 Hz
                                        2
         Shock Resistance  Damage limits: 500m/s  (Approx. 50G)
                          24V AC type: 1.6 VA
                          24V DC type: 1.0W
                   GE1A-B
                          110V AC type: 3.8 VA
     Terminal Blocks  Consumption  GE1A-C  24V AC type: 2.0 VA
                          220V AC type: 7.7 VA
         Power
                          24V DC type: 0.8W
                          110V AC type: 3.5 VA
                          220V AC type: 8.0 VA
         Electrical Life  100,000 operations minimum (at full rated load)
         Mechanical Life  10,000,000 operations minimum
         Operating Temperature  –10 to +55°C (without freezing)
     Circuit Breakers
         Operating Humidity
                          35 to 85% RH (without freezing)










      844                                               www.idec.com