ACCESSORIES                                                                        61




          —
          Ordering information for accessories IEC and UL
          Auxiliary contacts












                           Auxiliary contact blocks, IP20
                           Contact numbering according to EN 50013. The type and the ordering numbers are for one piece.

                           —
                           Auxiliary contacts
                           Mounting under the mechanism cover.
                           OTDC S1.0 - OTDC100…250E, OTDC100…200U_: Max. 4 test contacts or 2 test contacts + 2 test indication contacts.
                           OTDC S2.0 - OTDC100…250G, OTDC100…250UG_: Max. 1 test contact + 1 test indication contact.
                           OTDC M - OTDC315…1000F_, OTDC250…1000UF_: Max. 4 test contacts + 4 test indication contacts.   06
                           Suitable                                                                      Pieces/
          —
          OA1G10, OA3G01   for switches               Function  Type  Order code                         Package
                                                      1NO    OA1G10   1SCA022353R4970                    10
                           OTDC100...1000_
                                                      1NC    OA3G01   1SCA022456R7410                    10
                           —
                           Module for auxiliary contacts
                           Screw mounting to the left side of the switch. Max. 8 auxiliary contact blocks with the OEA28 module.
                           Suitable                                                                      Pieces/
                           for switches                      Type     Order code                         Package
                           OTDC S1.0 - OTDC100…250E, OTDC100…200U_  OEA28  1SCA022714R8810               1


                           —
                           Performance data according to IEC 60947-5-1
                           For OA1G, OA3G
                                        AC15                    DC12                    DC13
                            U /[VAC]    I /[A]      U /[V DC]   I /[A]      P/[W]       I /[A]      P/[W]
                                        e
                                                     e
                             e
                                                                                        e
                                                                e
                            230         6           24          10          240         2           50
                            400         4           72          4           290         0.8         60
                            415         4           125         2           250         0.55        70
                            690         2           250         0.55        140         0.27        70
                            -           -           440         0.1         44          -           -