Page 155 - Sace Emax 2 Catalogue
P. 155

INSTALL ATION                                                                     7/21



































 HR Terminal   HR Terminal                  VR Terminal                       VR Terminal
 One circuit breaker in the column   Two circuit breakers in the column   One circuit breaker in the column   Two circuit breakers in the column








 Environment temperature   Environment temperature   Environment temperature   Environment temperature
 IP  Iu  Connection  [mm]  Compartment  35 °C  45 °C  55 °C  35 °C  45 °C  55 °C  35 °C  45 °C  55 °C  35 °C  45 °C  55 °C
 IP31   2  800       800        800                                           800        800        800
 800  1x60x10
 1  800  800  800  800  800     800         800        800        800         800        800        800
 2        1000       1000       1000                                          1000       1000       1000
 1000  1x60x10
 1  1000  1000  1000  1000  1000  1000      1000       1000       1000        1000       1000       1000
 2        1250       1250       1250                                          1250       1250       1250
 1250  2x60x10
 1  1250  1250  1250  1250  1250  1250      1250       1250       1250        1250       1250       1250
                                                                                                                       07
 2        1470       1410       1360
 2x60x10
 1  1600  1540  1480  1550  1490  1430
 1600
 Compartment 2  2                                                             1500       1470       1400
 1x100x10
 1                                          1600       1600       1520        1580       1550       1475
 2        1920       1810       1720
 Compartment 1  3x60x10  1  2000  1940  1850  1950  1850  1760
 2                                                                            1950       1860       1760
 2x80x10
 1                                          2000       2000       1920        2000       1920       1810
 2000
 2        2000       1900       1810
 3x60x10 *
 1  2000  2000  1940  2000  1945  1850
 2                                                                            2000       1950       1850
 2x80x10 *
 1                                          2000       2000       2000        2000       2000       1900
 2        2280       2200       2100
 3x60x10
 1  2400  2320  2200  2400  2310  2170
 2                                                                            2400       2270       2160
 4x100x5
 1                                          2500       2450       2350        2500       2380       2270
 2500
 2        2394       2310       2205
 3x60x10 *
 1  2500  2460  2320  2500  2430  2280
 2                                                                            2500       2390       2270
 4x100x5 *
 1                                          2500       2500       2460        2500       2500       2380
 * Performances refer to SHR and SVR terminals.
 Performances with F and FL terminals can be compared to the performance of circuit breakers with HR terminals.
 Performances depend on switchboard design and testing condition. ABB is not responsible for the overall performances result.