INSTALL ATION                                                                    7/23





















                           The following tables provide an indication of the
                           performance of the apparatus inside the switch-
                           gear. The data shown are a summary of software
                           model simulations and real tests.

                           SACE Emax 2 E6.2 H V X Circuit-breaker
                           Switchgear dimensions 2200x1200x900 (HxLxD)



                                                              HR Terminal              VR Terminal
                                                              One circuit breaker in the column   One circuit breaker in the column








                                                              Environment temperature   Environment temperature
          IP                         Iu   Connection  Compartment 35 °C  45 °C  55 °C  35 °C   45 °C    55 °C
                                          [mm]
          IP31


                                     4000  4x100x10  1        4000    4000     4000    4000    4000     4000


                                                                                                                       07

          Compart-
          ment 2                     5000  5x100x10  1        5000    5000     4900    5000    5000     5000



          Compart-
          ment 1

                                     6300  6x100x10  1        5650    5350     5100    6000    5700     5250




          Performances with F and FL  terminals can be compared to the performances of circuit breaker with HR terminal.