9/6              SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Reading information


          Circuit-breakers









                           Notes                                       K)  Only for E2.2, E4.2 and E6.2 withdrawable
                           A)   Auxiliary supply for Ekip trip unit is mandatory   version circuit-breakers as an alternative to
                              ( refer to diagram 1SDM00009R0001 figures   Fig. 31-32-33.
                              31 - 32- 33 - 34).                       L)   In the presence of Fig. 32, for E2.2, E4.2 and
                           B)   When there are mixed auxiliary contacts Q1   E6.2 circuit-breakers up to three applications
                              and Q2 are 400V, while Q3 and Q4 are 24V.   between Fig. 41…58 taken only once can be
                              Then Q5, Q6, Q7 are 400V, while Q8, Q9, Q10   supplied, instead for E1.2 circuit-breakers, up
                              are 24V.                                    to two applications between Fig. 41…58 taken
                           C)  Always supplied with Ekip Com module.      only once can be supplied. The Ekip Com
                           D)  Always supplied with motor for loading     module selected can be duplicated if required,
                              closing springs in Fig. 13.                 by choosing between Fig. 61…66.
                           E)   Obligatory voltage transformer in the case of   M)  In the presence of Fig. 33, for E2.2, E4.2 and
                              external sockets. Obligatory external sockets   E6.2 circuit-breakers, up to two applications
                              for systems with rated voltage greater than   between Fig. 41…58 taken only once can be
                              690V.                                       supplied. The Ekip Com module selected can
                           F)   The connections between the RC residual cur-  be duplicated if required, by choosing
                              rent protection sensor and the poles of the X   between Fig. 61…66.
                              connector (or XV) of the circuitbreaker must   N)  In the presence of Fig. 34, for E2.2, E4.2 and
                              be made with 4-pole shielded cable with     E6.2 circuit-breakers, a single application
                              conductors interwoven in pairs (type BELDEN   between Fig. 41…58 can be supplied.
                              9696 paired or equivalent), of a length no   O)  In the presence of several Ekip Com modules
                              greater than 10 m. The shield should be     with withdrawable version circuit-breakers,
                              earthed on circuit-breaker side.            the contact S75I/5 should be connected only
                           G)  With all electronic protection trip units   once to a single module.
                              equipped with display interface with LSIG    P)   The auxiliary voltage Uaux. enables activation
                              protections, protection against an earth fault  of all the functions of the EKIP electronic
                              is available (Gext) by means of current sensor   protection trip units. Since an earth insulated
                              positioned on the star centre of the MV/LV   Uaux was requested, it is necessary to use
                              transformer. The connection between         “galvanically separated convertors” which
                              terminals 1 and 2 of the UI/O current       comply with the standards IEC 60950
                              transformer and Ge+ and Ge- poles of the X   (UL 1950) or equivalent, which guarantee a
                              connector (or XV) must be made with shielded   common mode current or leakage current
                              and stranded 2-pole cable (type BELDEN 9841   (refer to IEC 478/1, CEI 22/3) no greater than
                              or equivalent) of length no greater than 15 m.  3.5mA, IEC 60364-41 and CEI 64-8.
                           H)  The connection between the terminal box and   Q)  Regarding local bus the maximum cable
                              external neutral sensor must be made with   lenght is 15m.
                              the 2m cable provided. For three pole circuit-   R)   Suggested RJ45 cable: CAT6 STP.
                              breakers, the Ne+ and Ne- poles of the X   T)   Connect terminals 120 Ω on if you want to  insert
                              connector (or XV) must be short-circuited if   a termination resistance on the Local Bus.
                              no sensor is present on the external neutral
                              conductor.
                           I)   Obligatory in the case of the presence of any
                              Ekip module.
                           J)   Only for E2.2, E4.2 and E6.2 withdrawable
                              version circuit-breakers as an alternative to
                              Fig. 31-32-34.
                           K)  Only for E2.2, E4.2 and E6.2 withdrawable
                              version circuit-breakers as an alternative to
                              Fig. 31-32-33.