Page 32 - Sace Emax 2 Manual Touch Protection breakers
P. 32

Continued from the previous page                                                             ABB | SACE Emax 2

       Summary table Standard Protections
                                        Threshold                   Calculation for- Calculation
        ABB      ANSI  (1)  Threshold                 Time                                      Tolerance t   (3)
                                        tolerance  (3)              mula t   (2)(9)(10)(11)  example t   (2)   t
                                                                          t                 t
                                        Activation for                            t  =  6.75 s with:
        L                 I1 = 0.4…1 In               t1 = 3…144 s  t  =            t           ± 10 % with If ≤ 6 In
                                                                     t
        (60947-2)  49     step = 0.001 In  If in the range   step = 1 s  (9 t1) / (If / I1)  2  I1 = 0.4 In; t1 = 3   ± 20 % with If > 6 In
                                        (1.05...1.2) x I1                         s; If = 0.8 In
        L                               Activation for              t  =
                                                                     t
        (60255-  49       I1 = 0.4…1 In  If in the range   t1 = 3…144 s  (t1 x a x b) / ((If /   See the table   ± 10 % with If ≤ 6 In
        151)              step = 0.001 In  (1.05...1.2) x I1  step = 1 s  I1) -1)  below        ± 20 % with If > 6 In
                                                                       k
                                        ± 7 % with If ≤                                         The better of the two
        S        50 TD    I2 = 0.6...10 In  6 In      t2 = 0.05…0.8 s  t  = t2    -             values:
        (t = k)  (13)     step = 0.1 In  ± 10 % with If   step = 0.01 s   t
                                        > 6 In                                                  ± 10 % or ± 40 ms
                                        ± 7 % with If ≤
        S                                                                         t  =  5 s con:
                                                                                    t
        (t = k / I    51  I2 = 0.6...10 In  6 In      t2 = 0.05…0.8 s  t  =   2   I2 = 1 In; t2 = 0.8   ± 15 % with If ≤ 6 In
                                                                     t
        )
        2  (13)           step = 0.1 In  ± 10 % with If   step = 0.01 s  (100 t2) / (If)  s; If = 4 In  ± 20 % with If > 6 In
                                        > 6 In
                                        ± 7 % with If ≤
        S2                I5 = 0.6...10 In  6 In      t5 = 0,05…0,8 s                           The better of the two
        (t = k)  (13)  50 TD  step = 0.1 In  ± 10 % with If   step = 0.01 s  t  = t5  -         values:
                                                                     t
                                                                                                ± 10 % or ± 40 ms
                                        > 6 In
                          I3 = 1.5...15 In
        I        50                     ± 10 %        Not adjustable  t  ≤ 30 ms  -             -
                          step = 0.1 In                              t
                                                      t4 =
        G                 I4 = 0.1...1 In             Instantaneous…1                           The better of the two
                             (4)
        (t = k)  (12)(13)  50N TD  step = 0.001 In  ± 7 %  s, 0.1...1s  t  = t4   -             values:        (8)
                                                                     t
                                                                                                ± 10 % or ± 40 ms
                                                      step = 0.05 s
        G                 I4 = 0.1...1 In             t4 = 0.1…1 s  t  =          t  =  0.32 s with:
                             (4)
                                                                                    t
        (t = k / I )  51N               ± 7 %                        t      2     I4 = 0.8 In; t4 =   ± 15 %
              2
        (12)(13)          step = 0.001 In             step = 0.05 s  2 / (If / I4)  0.2 s; If = 2 In
                          I31 = 1.5...15 In
        2I       50                     ± 10 %        Not adjustable  t  ≤ 30 ms  -             -
                          step = 0.1 In                              t
                          I3 = 1.5...15 In            40…500 ms  (5)
        MCR      -                      ± 10 %                      t  ≤ 30 ms    -             -
                          step = 0.1 In               step = 0.01 s   t
                                                                                                the better of the two
                                                                                                values:
                          I6 = 2…90 %                 t6 = 0.5…60 s                             ± 10 % or ± 40 ms
        IU       46                     ± 10 %                      t  = t6       -
                          step = 1 %                  step = 0.5 s   t                          (for a time set < 5 s) /
                                                                                                ± 100 ms (for a time
                                                                                                set ≥ 5 s)
                                                                                               Continued on the next page




























       30 | © 2019 ABB |  1SDH001316R1002 - ECN000086501 - Rev. A                          Protections | 2 - Standard Protections