       6 - Power protections

         List
         The Power protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in Ekip Touch as additional
         SW package, are:

          Name      Type of protection                  Threshold    Time    Additional functions  (3)
         RP         Reverse active power                                     Trip enable, Block
                                                                             Trip enable, Directional Zone Selectivity , Startup
                                                                                                          (4)
         D  (2)     Directional short-circuit with adjustable delay
                                                                             enable, Block, Direction Min Angle
         OQ  (1)    Maximum reactive power                                   Trip enable, Block
         OP  (1)    Active overpower                                         Trip enable, Block
         UP  (1)    Active underpower                                        Trip enable, Block, Startup enable
         RQ  (1)(2)  Reverse reactive power                                  Trip enable, Block
         Cos φ      Minimum Cos φ

         Further details about the protections are given in document 1SDH001330R1002.

         (1)  the protection is not available by default with Ekip Hi-Touch. However, it can be integrated by requesting the relative SW package
         (2)  the protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
         (3)  Block configuration available via Ekip Connect
         (4)  Directional Zone Selectivity functions as an alternative to Zone Selectivity S and G


                WARNING! The Power flow parameters effect the sign of the power and power factor values measured by the unit.
                Power flow must be configured and verified on the basis of your installation to ensure that all the protections of the
                Power Protections package function correctly
         Summary table
                                                                            Calculation
                                                  Tolerance
          ABB  ANSI  (7)  Threshold                            Time         formula   Tolerance t   (6)
                                                  threshold                                      t
                                                                            t   (5)
                                                                             t
                                                                                      The best of the two values: ± 10% or
                       P11 = -1...-0,05 Sn step = 0,001       t11 = 0,5...100 s
         RP    32R                               ± 10 %                     t  = t11  ±  40 ms (for set time < 5 s) / ±  100
                       Sn                                     step = 0,1 s   t
                                                                                      ms (for set time ≥ 5 s)
                                                              t7 Fw/Bw =              ± 40 ms (for t7 ≥ 400 ms) / whichever
                       I7 Fw/Bw = 0,6...10 In step = 0,1   ± 7 % If ≤ 6 In
         D  (8)  67                                           0,1...0,8 s step  t  = t7  is higher, ± 20 ms or ± 10 % (for t7 <
                       In                        ± 10 % If > 6 In            t
                                                              = 0,01 s                400 ms)
                                                                                      The best of the two values: ± 10% or
                                                              t27 = 0,5...100 s
         OQ    32OF    Q27 = 0,4...2 Sn step = 0,001 Sn  ± 10 %             t  = t27  ±  40 ms (for set time < 5 s) / ± 100
                                                              step = 0,5 s   t
                                                                                      ms (for set time ≥ 5 s)
                                                                                      The best of the two values: ± 10% or
                                                              t26 = 0,5...100 s
         OP    32OF    P26 = 0,4...2 Sn step = 0,001 Sn  ± 10 %             t  = t26  ±  40 ms (for set time < 5 s) / ± 100
                                                              step = 0,5 s   t
                                                                                      ms (for set time ≥ 5 s)
                                                                                      The best of the two values: ± 10% or
                                                              t23 = 0,5...100 s
         UP  (9)  32LF  P23 = 0,1...1 Sn step = 0,001 Sn  ± 10 %            t  = t23  ±  40 ms (for set time < 5 s) / ± 100
                                                              step = 0,5 s   t
                                                                                      ms (for set time ≥ 5 s)
                       Q24 = -1...-0,1 Sn step = 0,001                                The best of the two values: ± 10% or
         RQ    40 / 32R Sn; Kq = -2…2 step = 0,01; Vmin  ± 10 %  t24 = 0,5...100 s   t  = t24  ±  40 ms (for set time < 5 s) / ± 100
                                                                             t
                       = 0,5...1,2 Un step = 0,01             step = 0,5 s            ms (for set time ≥ 5 s)
         Cos φ 78      Cos φ = 0,5...0,95 step = 0,01
         (5)  calculation of t  is valid for values which have exceeded the trip threshold of the protection
                      t
         (6)  tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values within
         operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
         (7)  ANSI / IEEE C37-2 codification
         (8)  the protection does not detect the fault current direction for < 5 V voltages.