Page 17 - Sace Emax 2 Manual for design engineers
P. 17
ABB | SACE Emax 2
2 - Ekip Touch models and versions
Default functions and Every Ekip Touch module has default measurement and protection functions, which can be extended with the
extensions aid of additional software packages.
The extensions (additional SW packages) can be pre-engineered when the circuit-breaker is ordered or at a
later date (in this case, via ABB Ability Marketplace TM
Overview
Figure 3
Ekip Ekip Ekip G
Model Ekip Touch
Hi-Touch G Touch Hi-Touch Page
Versions LSI, LSIG LSI, LSIG LSIG LSIG
Standard protections X X X X 52
Voltage protections O (1) X X (3) X 62
Voltage advanced O (1) O X (3) X 65
protections
Frequency protections O (1) X X (3) X 69
Power protections O (1) X (3) X (3) X 72
ROCOF protections O (1) O O X 78
Adaptive protections O X O X 79
Standard Measurements X X X X 110
Ekip Measuring O X X X 114
Measurements
Class 1 Power & Energy (2)
Metering O X O X 117
Datalogger O (1) X X X 118
Network Analyzer O (1) X O X 120
X = Available by default; O = Optional
(1) Configurable if Measuring Measurements package is present
(2) Only available at the time circuit-breaker is ordered
(3) Certain protections of the complete package are available by default; the remaining ones can be activated
on request
15 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Trip unit Overview | 2 - Ekip Touch models and versions