Page 17 - Sace Emax 2 Manual for design engineers
P. 17

ABB | SACE Emax 2
       2 - Ekip Touch models and versions



                Default functions and  Every Ekip Touch module has default measurement and protection functions, which can be extended with the
                         extensions aid of additional software packages.
                                    The extensions (additional SW packages) can be pre-engineered when the circuit-breaker is ordered or at a
                                    later date (in this case, via ABB Ability Marketplace  TM



                          Overview
















                                    Figure 3

                                                                      Ekip       Ekip        Ekip G
                                     Model                 Ekip Touch
                                                                      Hi-Touch   G Touch     Hi-Touch   Page
                                     Versions              LSI, LSIG  LSI, LSIG  LSIG       LSIG
                                     Standard protections  X          X          X          X           52
                                     Voltage protections   O  (1)     X          X  (3)     X           62
                                     Voltage advanced      O  (1)     O          X  (3)     X           65
                                     protections
                                     Frequency protections  O  (1)    X          X  (3)     X           69
                                     Power protections     O  (1)     X  (3)     X  (3)     X           72
                                     ROCOF protections     O  (1)     O          O          X           78
                                     Adaptive protections  O          X          O          X           79
                                     Standard Measurements  X         X          X          X           110
                                     Ekip Measuring        O          X          X          X           114
                                     Measurements
                                     Class 1 Power & Energy    (2)
                                     Metering              O          X          O          X           117
                                     Datalogger            O  (1)     X          X          X           118
                                     Network Analyzer      O  (1)     X          O          X           120

                                    X  = Available by default; O = Optional
                                    (1)  Configurable if Measuring Measurements package is present
                                    (2)  Only available at the time circuit-breaker is ordered
                                    (3)  Certain protections of the complete package are available by default; the remaining ones can be activated
                                    on request






















       15 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                  Trip unit Overview | 2 - Ekip Touch models and versions
   12   13   14   15   16   17   18   19   20   21   22