        Ekip Dip




       1 - Operator interface



                        Introduction The operator interface of the Ekip Dip protection trip unit allows you to:
                                     •  Set the parameters relating to the available protections.
                                     •  View the status of the trip unit and alarms.
                                     •  Connect to the frontal connector to communicate and perform the opening test.


         Components of the interface The Ekip Dip operator interface appears as follows:
















                                    Figure 4

                                    The following table provides a description of the components of the interface:
                                     Position   Type               Description
                                     A                            L Protection LED (alarm and trip)
                                     B                            L Protection LED (pre-alarm)
                                     C                            S Protection LED (alarm and trip)
                                                LED
                                     D                            I Protection LED (trip)
                                     E                            G Protection LED (alarm and trip)
                                     F                            Power-on LED (trip unit powered and on)
                                     G                            L Protection dip-switch (threshold I1)
                                     H          Protections:      S Protection dip-switch (threshold I2)
                                     I          thresholds        I Protection dip-switch (threshold I3)
                                     L                            G Protection dip-switch (threshold I4)
                                     M                            L Protection dip-switch (time t1)
                                     N          Protections: times  S Protection dip-switch (time t2 and type of curve)
                                     O                            G Protection dip-switch (time t4 and type of curve)
                                     P          Settings          Neutral and frequency dip-switch
                                     Q          Test              Test pushbutton
                                     R                            Test connector

                                           IMPORTANT: the figure above refers to an Ekip Dip, LSIG version. In the case of Ekip
                                               Dip LI or LSI versions, LEDs and dip-switches related only to the protections
                                           present are available.


                              LEDs The LEDs are useful on Ekip Dip in order to distinguish and identify various types of information on the
                                    protection trip unit, the circuit-breaker and state of the line currents.
                                    Operational conditions
                                    The operation of the LED is determined by the power supply conditions of the trip unit:
                                     •  With the trip unit energized (by current sensors or by auxiliary power supply or by Ekip TT or by Ekip T&P)
                                       the LEDs are operational for all the signals.
                                     •  With the trip unit de-energized, the LEDs are limited to the signalling of the last switch-off or trip event
                                       (combined with the check via iTest, described below).
                                                                                                  Continued on the next page
       18 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                                Ekip Dip | 1 - Operator interface
   15   16   17   18   19   20   21   22   23   24   25