                        S Protection S protection protects against selective short circuit.
                                           NOTE: the protection is available for LSI and LSIG versions of the trip unit.

                  t   I2      S     When  the  activation  threshold  is  exceeded,  the  protection  trips  within  a  fixed  or  dynamic  time  (the  time
                                    decreases as the current reading increases).
                                    Parameters
                           t2       All the parameters that can be modified by the user affect the response curve, and related tripping times.

                                 I   Parameter      Description
                                     Enable         By setting the threshold dip-switches to the Off position, the protection is disabled.
                                                    It determines the dynamic of the curve and the tripping time, fixed or dynamic
                                                    according to the selection:
                                     Type of curve
                                                           NOTE: calculation of the tripping time of the inverse time curve is based on a
                                                        mathematical expression. The details are provided in the table on page 26.
                                                    It defines the current value that activates the protection when exceeded (with
                                                    reference to the curve, it is the part parallel to the y-axis).

                                                           IMPORTANT:
                                     Threshold I2
                                                          • The I2 threshold set must be higher than the I1 threshold. An
                                                        incorrect configuration returns an alarm signal.
                                                          • The delay is interrupted if the current drops below the activation
                                                    threshold.
                                                    The selected function determines the contribution of t2:
                                                     • Fixed time: t2 is the delay time between exceeding the I2 threshold and sending
                                                    the opening command.
                                                     • Dynamic time: t2 contributes in calculating the tripping time (with reference to the
                                                    curve, t2 affects the entire curve, shifting it as a whole along the vertical axis).
                                     Time t2
                                                          IMPORTANT:
                                                          •  The minimum tripping time of the protection is t2. If, according to
                                                        the calculation, the tripping time is less, it is automatically limited to t2.
                                                          •  For all the UL versions, the maximum time allowed is 0.4 s. If a
                                                    higher value is set, the trip unit signals the error and forces the parameter to
                                                    0.4 s.

                                    With the module Ekip T&P and with the Ekip Connect software, it is possible to activate the function Thermal
                                    Memory.