Page 255 - Sace Emax 2 Manual for design engineers
P. 255
ABB | SACE Emax 2
SL: shutter lock The SL shutter locks the shutters of the fixed part.
It is possible to lock the upper and lower shutters independently.
This is an accessory available on all the fixed parts and can work with the aid of padlocks with diameters of 4
mm - 0.16", 6 mm - 0.24", 8 mm - 0.32", with a maximum of four padlocks per fixed part (two for the upper
shutters and two for the lower shutters).
NOTE: The padlocks are at customer's expenses.
SL for E1.2 SL for E2.2 - E4.2 - E6.2
DLC: Door opening lock with The DLC prevents the following operations from being carried out:
the circuit-breaker in closed • opening the switchgear door with the circuit-breaker closed if the circuit-breaker is in fixed version
position • opening the switchgear door with the circuit-breaker closed and in connected position if the circuit-breaker
is in fixed version
• closing of the circuit-breaker when the switchgear door is open
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999r0712 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000r0712.
253 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Mechanical accessories | 2 - Mechanical safety accessories