            DLP : door opening lock  The DLP lock prevents the switchgear door from being opened when the moving part of the circuit-breaker
                 (1)
            with the circuit-breaker in  is in the connected or test position.
              connected/test position  It can be installed alternatively on the right side or the left side of the fixed part.

                                           NOTE: The DLP lock is used as an alternative to the mechanical interlock.














                                                                            DLP for E2.2 - E4.2 - E6.2
                                    (1)  Not available for E1.2
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
                                    particular with the kit sheet 1SDH001000r0709.


            DLR : lock on racking-in/ The DLR lock prevents the moving part from being racked in/out from the fixed part when the switchgear
                (1)
        racking-out of the moving part  door is open.
                  with the door open  It is available on request on all fixed parts.














                                                                            DLR for E2.2 - E4.2 - E6.2
                                    (1)  Not available for E1.2
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
                                    particular with the kit sheet 1SDH001000r0725.



                           Fail safe The fail safe is a device that prevents the removal of the mobile part of a withdrawable circuit-breaker from
                                    the fixed part if the springs are charged.
                                    It is always supplied with UL circuit-breakers.
                                           IMPORTANT:

                                            •  The fail safe device makes undervoltage coil YU unavailable.
                                            •  It is, however, possible not to install the fail safe device, in which case the undervoltage
                                              coil YU must be used.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
                                    particular for E1.2 in the kit sheets
                                     •  1SDH000999r0708 for the Fail Safe, movable part
                                     •  1SDH000999r0711 for the Fail Safe, fixed part
                                    and for E2.2-E4.2-E6.2 in the kit sheet 1SDH001400r0821.