       6 - Default parameters
                                    The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front DIPs
                                    (protections, Frequency, Neutral), other via front bus.
                                     Protection/Parameter                   Value
                                     L                                      1 In; 144 s
                                     S  (1)                                 Off; 0.1 s
                                     I                                      4 In
                                     G  (1)                                 Off; 0.1 s
                                     Frequency                              50 Hz (IEC) / 60 Hz (UL)
                                                                            Off (for three-pole circuit breakers).
                                     Neutral
                                                                            50 % (for four-pole circuit-breaker)
                                     Hardware Trip                          Disabled
                                     Local Bus                              Off
                                     Alive LED                              Disabled (Power-on LED fixed)
                                     Maintenance                            Off


                                    (1)  S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.


































































       34 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                               Ekip Dip | 6 - Default parameters