Page 36 - Sace Emax 2 Manual for design engineers
P. 36
ABB | SACE Emax 2
6 - Default parameters
The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front DIPs
(protections, Frequency, Neutral), other via front bus.
Protection/Parameter Value
L 1 In; 144 s
S (1) Off; 0.1 s
I 4 In
G (1) Off; 0.1 s
Frequency 50 Hz (IEC) / 60 Hz (UL)
Off (for three-pole circuit breakers).
Neutral
50 % (for four-pole circuit-breaker)
Hardware Trip Disabled
Local Bus Off
Alive LED Disabled (Power-on LED fixed)
Maintenance Off
(1) S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.
34 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Ekip Dip | 6 - Default parameters