Page 38 - Sace Emax 2 Manual for design engineers
P. 38

ABB | SACE Emax 2
                              LEDs   LEDs     Colour    Description
                                                        Indicates the on status of Ekip Touch:
                                                         • off: no power and unit off
                                     Power               • on, steady (Power mode) or flashing (Alive mode): unit on and self-supplied
                                              Green     by external Vaux or service connector
                                                        The Power mode or Alive mode can be selected via Ekip Connect: if the Alive
                                                        mode has been selected and external modules are connected, the Power leds
                                                        of Ekip Touch and the modules flash in the synchronized mode.
                                                        Signals that certain alarms are present:
                                     Warnings            • off: no alarm
                                              Yellow     • on steady: prealarm of an active protection or status contacts error
                                                         • two flast flashes every 0.5 s: trip unit parameter configuration error
                                                         • fast flash: Rating Plug or Measurement module installation error
                                                        Signals that an alarm is present:
                                                         • off: no alarm
                                                         • on steady: on steady signals a TRIP due to a protection
                                     Alarm               • on flashing: protection timing tripped or alarm due to disconnection of a
                                              Red
                                                        current sensor
                                                         • two flast flashes every 2 seconds: Rating Plug error
                                                         • on with fast flashing: protection timing tripped or alarm due to disconnection
                                                        of a current sensor


                                    If on at the same time, the Warning and Alarm leds provide further signals:
                                     •  leds on with fast flashing: no communication between Trip unit and Mainboard
                                     •  leds on with slow flashing: internal error
                                     •  leds on and steady internal configuration error
                                    These cases need assistance from ABB.


                       Push-buttons  Push-
                                     button   Description
                                              Allows different areas of the menu to be accessed:
                                     HOME      • from pages: HOME, Histograms, Measuring instruments, Measurements, Main
                                              measurements -> open: Main page
                                               • from pages: Main page, Alarm list, at any point of the menu area -> open: HOME page
                                              Allows certain pages of information about the unit to be rapidly consulted; press the button
                                              in successionj to display the following pages:
                                               • Alarm list, if messages are present
                                               • Info, if Customer Page option is active
                                               • Protection unit, with information about Ekip Touch
                                     iTest     • Circuit breaker, with information about the CB
                                               • Last trip, with information about the last trip, if available
                                              Consultation is active from pages: HOME, Histograms, Measuring instruments,
                                              Measurements, Main measurements
                                                  NOTE: with Ekip Touch off and the internal battery charged, press  iTEST  to
                                                  temporarily switch on the Power led and, in the case of a trip, the display with
                                                  information about the trip protection and the Alarm led




                  Service connector The service connector enables Ekip Touch to be connected to Ekip TT, Ekip T&P and Ekip Programming,
                                    allowing the unit to be temporarily supplied, parameter configuration prior to putting into service, tests and
                                    extension of the configuration functions.

                                           IMPORTANT: only use cables supplied by ABB or with ABB accessories

















       36 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A              Ekip Touch - Interface and menus | 1 - Presentation of interface
   33   34   35   36   37   38   39   40   41   42   43