               Additional protections  Protection                      Trip threshold
                                     [ANSI code]   Trip time t  t  (1)  tolerance  (3)  Trip time tolerance
                                                   t  = t41 ( with curve t = k )     The best between ± 10% and 40 ms
                                                     t
                                     Gext
                                     [50GTD / 51G]                     ± 7 %         ± 15 %

                                                                  2
                                                   (with curve t = k / I )
                                     Rc                                              140 ms @ 0,06 s  (9)
                                     [64 50N TD 87N]  t  = tdn         -20 % ÷ 0     950 ms @ 0,8 s  (9)
                                                     t
                                                   t = k                             The best between ± 10% and 40 ms
                                     MDGF                              ± 7 %
                                                   t = k / l  2                      ± 15 %

                                    Startup
                                     Protection    Trip time t   (1)  Trip threshold   Trip time tolerance
                                     [ANSI code]             t        tolerance  (3)
                                     Gext StartUp  t  = t41 startup   ± 7 %          the best between: ± 10 % and ± 40 ms
                                                     t



                 Note on protections  (1)  use trip and threshold current values expressed in In for calculating t  (example: If = 0.8 In, I1= 0.6 In)
                                                                                       t
                                    (2)  with t4 = instantaneous, the maximum tolerance is 50 ms
                                    (3)  Tolerance values valid with Trip unit at steady state or on with auxiliary power supply, trip time ≥ 100 ms,
                                    temperature and signals within operating limits; the tolerances in the table after the notes are applicable if the
                                    conditions are not guaranteed
                                    (4)  the trip unit considers a 3% hysteresis for clearing from the alarm condition
                                    (5)  tolerance valid for frequencies within range: fn ± 2 %. A ± 5% tolerance is applicable for off range
                                    frequencies
                                    (6)  ± 20% for threshold 0.4 Hz / s
                                    (9)  maximum trip time
                                    (10)  with If ≥ 18 kA, t  ≤ 3 ms;
                                                   t
                                        with 18 kA > If ≥ I31 * 3, t  ≤ 7 ms (If three-phase) or t  ≤ 9 ms (If single-phase);
                                                         t                   t
                                        with If < 18 kA and If < I31 * 3, t  ≤ 15 ms.
                                                              t
                                        (operating parameters guaranteed with Vaux auxiliary power supply)
                                    (11)  tolerance valid with threshold U14 > 10%; with U14 ≤ 10% (and >6%), the tolerance is 10%; with U14 <
                                    5%, the tolerance is 15%
                                    Performance guaranteed in all operating conditions
                                     Protection  Trip threshold tolerance      Trip time tolerance
                                     L         Activation within range: (1.05 to 1.2) x I1  ± 20 %
                                     S         ± 10 %                          ± 20 %
                                     I / 2I    ± 15 %                          ≤ 60 ms
                                     G         ± 15 %                          ± 20 % (60 ms with t4 = instantaneous)
                                     Gext      ± 15 %                          ± 20 %
                                     MDGF      ± 15 %                          ± 20 %
                                     UF / UF2 /    ± 2 %                       ± 20 %
                                     OF / OF2
                                                                               ± 20 %; in the case of single-phase self-supply:
                                     RV        ± 10 %
                                                                               the highest between ± 20 % and 30 ms
                                     Other     --                              ± 20 %