Page 195 - SACE Tmax XT - Catalogue
P. 195

ACCESSORIES                                                                      7/49



          —

          Interlocks and switching devices














                           Operating mechanism                         XT1  XT2  XT3  XT4  XT5  XT6  XT7  XT7 M
                           Rear mechanical   MIR Horizontal                                    -    -
                           interlock    MIR Vertical                                           -    -
                                        Type A (2 CBs)                 -    -    -    -    -    -        
                           Cables interlocks
                                        Type B, C and D (3 CBs)        -    -    -    -    -    -        
                           Automatic    ATS021                                                     
                           transfer switch  ATS022                                                 

                           Rear mechanical interlock
                           This is a support designed for installation on the rear of two circuit-breakers to be interlocked. It prevents
                           the two circuit-breakers it is installed on from closing simultaneously by linking components. Tmax XT cir-
                           cuit-breakers can be interlocked two-by-two (IO-OI-OO) by means of a chassis and special plates. Inter-
                           locked circuit-breakers can be in fixed, plug-in or withdrawable versions. Both circuit-breakers and
                           switch-disconnectors in the 3 and 4 pole versions can be interlocked.
          —                The allowed combinations are:
          Interlock
                                       XT1         XT2          XT3         XT4         XT5         XT6
                           XT1                                           
                           XT2                                           
                           XT3                                           
                           XT4                                                      
                           XT5                                                                    
                           XT6                                                                     

                           The following equipment must be ordered to make a rear interlock:                           07
                           •  a vertical or horizontal chassis;
                           •  a plate for each circuit-breaker to be interlocked.
                           For using an XT4 on an XT5 chassis and an XT5 on an XT6 chassis, dedicated plates are necessary.
                           Please note that remote closing commands sent to interlocked circuit-breakers in the open position
                           must be prevented in order to ensure the correct functioning of the mechanical interlock. If this is not
                           possible, key locks in the open position for the MOE are necessary.
                           With the XT5 and XT6 interlock chassis, for withdrawable version circuit-breakers, the use of the key-
                           lock/padlock for fixed parts (KLF) is not allowed.




                                              +                             =






                            —                      —                             —
                            Interlock - Chassis    Two plates                    Interlock