Page 193 - SACE Tmax XT - Catalogue
P. 193
ACCESSORIES 7/47
Lock for thermal regulation
Type of lock Circuit- Optional/ Position Type of lock Removability
breaker standard of circuit- of key
supply breaker lock
Lock for XT1, XT3 Optional - - -
Trip Unit thermal XT2, XT4, standard - - -
regulation (1) XT5, XT6
(1) This is applied to the cover of the circuit-breakers on level with the regulator of the thermal element of the thermal-magnetic release TMD
and prevents it from being tampered with.
Lock for shutters of fixed parts
Type of lock Circuit- Optional/ Position Type of lock Removability
breaker standard of circuit- of key
supply breaker lock
Shutter XT7, Optional - Padlocks max 3 padlocks Ø 8mm stem -
Fixed Part
lock - SL XT7 M (not supplied)
IP Protection Kit
In order to improve the IP protection degree, some additional kits can be used.
07
IP54 Protection flange for direct rotary handle (RHD)
This flange can be mounted with the direct rotary handle of the XT5, XT6 and XT7 to guarantee an IP54
degree of protection.
With this flange is not possible to open the panel door when the circuit-breaker is in the closed position.
IP54 Protection for transmitted rotary handle (RHE)
This device can be fixed onto the transmitted rotary and lateral handle of the XT1, XT2, XT3 and XT4 al-
lowing an IP54 degree of protection to be achieved. The IP degree of the transmitted rotary handle for
the XT5, XT6 and XT7 is IP65 as standard without an additional accessory.
—
IP54 protection
IP54 Protection flange for the MOE and XT7 M
This transparent cover completely protects the front of the circuit-breaker, guaranteeing an IP54 degree
of protection. This accessory is provided with a double key lock (same or different keys).
This cover is available for the XT5 MOE/MOE-E, XT6 MOE and for the XT7 M circuit-breaker.
—
IP54 protection
for XT7 M