Page 125 - Surge-Protection-E_0.pdf
P. 125
Measuring Devices and Accessories
Wiring Accessories DK
• Allows changing of the wiring level
• For lightning current suitable installation of arrester
combinations
Uniform wiring level from the top thanks to DK 25 feed-through terminal.
Feed-Through Terminal DK 25 952 699 DK 25
Feed-through terminal for busbar wiring.
952 699 4013364127906 04 01 04 03 103 g
36,50 €
Type DK 25
Part No. 952 699
Nominal voltage (a.c. / d.c.) (UN) 500 V
Nominal load current (a.c.) (IL) 100 A
Lightning impulse current (10/350 µs) 100 kA
Cross-sectional area (min.) 1.5 mm solid / flexible
2
2
Cross-sectional area (max.) 25 mm stranded / 16 mm flexible
2
Wiring Accessories STAK
• EMC-optimised series connection according to IEC 60364-5-53
STAK 2X16 for EMC-optimised se-
ries connection of lightning current
and surge arresters according to STAK 3X16 for EMC-optimised series connection of string lines in a PV generator
IEC 60364-5-53. junction box.
STAK 25 Pin-shaped Terminal 952 589 STAK 25
Pin-shaped terminal for EMC-optimised series connection of lightning current and surge arresters according to IEC 60364-5-53.
952 589 4013364132306 04 01 04 03 17 g
8,20 €
Type STAK ... 25
Part No. 952 589
Nominal voltage (a.c. / d.c.) (UN) 600 V
Max. PV voltage (UCPV) when used in 1200 V
combination with DEHNguard M YPV ...
Lightning impulse current (10/350 µs) 25 kA
Discharge current (8/20 µs) 50 kA
Cross-sectional area (min.) 1.5 mm solid / flexible
2
2
2
Cross-sectional area (max.) 25 mm stranded / 16 mm flexible
Type of connection front
STAK 2X16 Pin-shaped Terminal 900 589 STAK 2X16 900 588 STAK 3X16
Pin-shaped terminal for EMC-optimised series connection of lightning current and surge arresters according to IEC 60364-5-53.
Type STAK ... 3X16 2X16 900 589 4013364109339 04 01 04 03 20 g 900 588 4013364323933 04 01 04 03 31 g
8,10 €
11,70 €
Part No. 900 588 900 589
Nominal voltage (a.c. / d.c.) (UN) 690 V / 1000 V ––
Load current at V-wiring 80 A ––
Lightning impulse current (10/350 µs) 25 kA 25 kA
Cross-sectional area (min.) 1.5 mm solid / flexible 2x 1.5 mm Measuring Devices and Accessories
2
2
Cross-sectional area (max.) 16 mm 2 stranded / 10 mm flexible 2x max. 16 mm 2
2
Type of connection front front (double terminal)
Valid as of August 1, 2020 You will find detailed product information on our website 121