Surge Arresters – Type 3


        SFL Protector
                                                             • Surge protection with monitoring device and disconnector
                                                             • Interference suppressor filter
                                                             • Enhanced safety due to fault-proof Y protective circuit
                                                             • Mains switch with operating state indication (SFL PRO 6X only)
                                                             • 2 m connection cable for flexible use in a wide range
                                                               of applications
                                                             • Visual operating state (green) and fault indicator (red)







        Multiple socket outlet for protecting the power supply circuits of electronic equip-
        ment against transients and high-frequency interference voltages. For installation
        in conformity with the lightning protection zone concept at the boundaries from
        1 – 2 and higher.



        SFL PRO 6X:    Surge protective multiple socket outlet with interference suppressor filter
        SFL PRO 6X 19":   Surge protective multiple socket outlet with mains filter for 482.6 mm (19 inch) data cabinets


        The SFL Protector surge arrester complements the wide range of Red/Line
        surge protective devices. The combination of surge protection and mains
        filter makes the six-way socket outlet a powerful device for protecting
        electronic consumers in final circuits. The harmonised surge protection and
        filter functions complement one another and prevent core saturation of
        the filter in case of high-level transients. The integrated mains filter is
        optimised for protection against balanced and unbalanced high-frequen-
        cy interferences. The nominal current carrying capability of 16 A allows
        flexible use of these devices in final circuits.
        The fault-proof Y protection circuit ensures protection even if the phase
        and neutral conductor in standard earthed socket outlets cannot be iden-
        tified. The standard green and red LEDs indicate the operating state of the
        surge protective device.
        The SFL PRO 6X 19" has been specifically developed for use in network
        cabinets and therefore provides optimal protection for terminal equip-
        ment in this critical field of application.




                         SFL PRO 6X
        909 250   SFL PRO 6X
                         Surge protective multiple socket outlet with mains filter.
        909 250   4013364132566  04 01 03 03   1.10
        kg         182,40 €
                          Type SFL PRO ...                  6X
                          Part No.                          909 250
                          SPD according to EN 61643-11 / IEC 61643-11  type 3 / class III
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Nominal discharge current (8/20 µs)  (In)  3 kA
                          Total discharge current (8/20 µs) [L+N-PE]  (Itotal)  5 kA
                          Voltage protection level  (UP)    ≤ 1.5 kV
                          Max. mains-side overcurrent protection  B 16 A
                          Number of socket outlets          6
    Surge Arresters – Type 3  909 251  909 251  kg      4013364132573  04 01 03 03   1.00   SFL PRO 19"  6X 19"
          SFL PRO 6X 19"
                         Surge protective multiple socket outlet with mains filter for 482.6 mm (19 inches) data cabinets.

          210,40 €
                          Type SFL PRO ...
                          Part No.
                                                            type 3 / class III
                          SPD according to EN 61643-11 / IEC 61643-11  909 251
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Nominal discharge current (8/20 µs)  (In)  3 kA
                          Total discharge current (8/20 µs) [L+N-PE]  (Itotal)  5 kA
                          Voltage protection level  (UP)    ≤ 1.5 kV
                          Max. mains-side overcurrent protection  B 16 A
                          Number of socket outlets          6