Page 191 - Surge-Protection-E_0.pdf
P. 191

Compact SPDs – DIN Rail Mounted


           DEHNconnect SD2 Ex (i)
           • Terminal block with integrated surge protection
               – For protecting intrinsically safe measuring and control circuits
              and bus systems (Ex (i))
               – Maximum impulse current carrying capability Imax up to
              20 kA (8/20 µs)
               – Low voltage protection level, capable of protecting terminal
              equipment
               – Approvals: ATEX, IECEx
           • Modular disconnection function
               – Disconnection module for disconnecting the signal circuit for
              maintenance work
               – Module fixing and mechanical ejector
               – Module in "parked" position after disconnection
           • Space-saving and function-optimised design
               – Terminal block with integrated surge protection (width of 6 mm)
               – Fast conductor connection without tools thanks
              to direct plug-in technology                                                                             DIN Rail Mounted
               – Can be used with jumper bar (accessory)                                                              Compact SPDs –

                                                                Arrester group for protecting intrinsically safe measuring circuits



           The DIN rail mounted surge arresters of the DEHNconnect SD2 series are   Conductors are connected via a vibration-proof spring-loaded connection
           designed as space-saving terminal blocks with a width of 6 mm. These   system. Stripped solid conductors and flexible conductors with wire end
           terminal blocks with integrated surge protection have a modular discon-  ferrule can be easily and quickly inserted into the relevant conductor ter-
           nection function that allows them to disconnect the signal circuit for   minal without tools. For rewiring, the conductor is removed from the
           maintenance work. An integrated module ejector disconnects the signal   clamping point and clamped into a new conductor terminal.
           circuit from the terminal equipment. The disconnection module does not   To reduce wiring, jumper bars can be inserted on the protected side of the
           have to be removed, but remains in a "parked" position in the module   surge arrester, thus quickly connecting signal circuits.
           slot.                                                The arresters are ideally suited for use in the process industry to protect
           DEHNconnect SD2 Ex (i) is designed for intrinsically safe measuring and   Ex  (i)  measuring  circuits  and  interfaces  for  bus  communication  (e.g.
           control circuits and bus systems and protects one unearthed pair (bal-  Fieldbus Foundation or Profibus PA).
           anced interface).










           Disconnection module with ejector –   Marking of the protected side – mini-  Terminals with direct plug-in technol-  Slots  for  jumper  bars  –  for  quickly
           for disconnecting the signal circuits.  mises wiring errors.  ogy – fast and vibration-proof con-  connecting signal circuits.
                                                                nection without tools.



           DCO SD2 MD EX                                                                                    917 960   DCO SD2 MD EX 24
           Surge arrester with energy-coordinated low-capacitance protective circuit and disconnection module for disconnecting signal circuits.
           For protecting one pair in intrinsically safe measuring circuits and bus systems, meets FISCO requirements. Self-capacitance and self-induct-  917 960        4013364150638  04 02 02 02   32 g
                                                                                                             71,20 €
           ance negligibly small. Insulation strength > 500 V to earth.
           Type                                 DCO SD2 MD EX 24
           Part No.                             917 960
           SPD class                            T
           Max. continuous operating voltage (d.c.)  (UC)  33 V
           Max. input current according to EN 60079-11  (Ii)  0.5 A
                                                                                                 1             1‘
           D1 Lightning impulse current (10/350 µs) per line  (Iimp)  1 kA                                     protected
           C2 Total nominal discharge current (8/20 µs)  (In)  10 kA                             2             2‘
           Cut-off frequency line-line  (fG)    5.8 MHz
           Approvals                            UL, CSA, EACEx, ATEX, IECEx, SIL












           Valid as of August 1, 2020                        You will find detailed product information on our website   187