Page 252 - Surge-Protection-E_0.pdf
P. 252

Isolating Spark Gaps


        EXFS 100 / EXFS 100 KU
                                                             • For indirect connection / earthing of functionally isolated parts
                                                               of installations under lightning conditions
                                                             • Device for lightning equipotential bonding according
                                                               to IEC 62305 in hazardous areas
                                                             • For bridging insulating joints, insulating flanges,
                                                               etc. in cathodically protected pipe sections
                                                             • For safe installation in Ex zone 1 (gas) or 21 (dust)
                                                             • Extremely low sparkover voltage
                                                             • Extremely high alternating current withstand capability
                                                             • Approval according to ATEX directive 94/9/EC, IECEx, UL
                                                               and Inmetro
    Isolating Spark Gaps  ATEX and IECEx-certified isolating spark gap with a low sparkover voltage for


        lightning equipotential bonding according to IEC 62305.



        EXFS 100:    Isolating spark gap for use in hazardous areas with plastic sheath and M10 threaded bushings
        EXFS 100 KU: Isolating spark gap for use in hazardous areas with two 2 m long connecting cables for underground installation



        The Ex isolating spark gaps of the EXFS 100 / EXFS 100 KU product fam-  The ATEX and IECEx-certified EXFS 100 and EXFS 100 KU spark gaps pro-
        ily are used when conductive installation parts situated in hazardous   vide approved safety according to harmonised European standards.
        areas cannot be directly interconnected.             Prewired connection cables in different lengths are available as accesso-
        The spark gaps with low sparkover voltage are especially efficient for   ries for connecting EXFS 100 spark gaps. Flat and angled connection brack-
        isolated parts of installations with low insulation strength.  ets (IF) enable simple connection of the spark gaps to pipeline flanges.
        No special requirements have to be observed for safe installation in zone   EXFS 100 KU Types are enclosed by a water-proof plastic sheath and are
        1 (gases) or zone 21 (dusts).                        therefore ideally suited for underground installation on insulating cou-
        With a maximum lightning impulse current of 100 kA (10/350 µs), EXFS   plings.
        100 and EXFS 100 KU meet class H requirements (highest lightning cur-
        rent carrying capability class).




                         EXFS 100
        923 100   EXFS 100
                         Isolating spark gap for use in hazardous areas with plastic sheath and M10 threaded screws.
        923 100   4013364108325  04 01 05 02   289 g
              269,50 €
                          Type EXFS ...                        100
                          Part No.                             923 100
                          Isolating spark gap according to EN 62561-3 / IEC 62561-3  yes
                          Lightning impulse current (10/350 µs)  (Iimp)  100 kA
                          Class (lightning current carrying capability)  H
                          Rated impulse sparkover voltage  (Ur imp)  ≤ 1.25 kV
                          Degree of protection                 IP 67
                          Approvals                            UL, Inmetro
                          ATEX approvals                       DEKRA 11ATEX0178 X
                          Ex marking according to EN 60079-0 and EN 60079-1: gas  II 2 G Ex db IIC T6 Gb
                          Ex marking according to EN 60079-0 and EN 60079-31: dust  II 2 D Ex tb IIIC T80 °C Db IP 66/67
                          IECEx approvals                      IECEx KEM 09.0051X
                          Ex marking according to EN 60079-0 and EN 60079-1: gas   Ex db IIC T6 Gb
                          Ex marking according to EN 60079-0 and EN 60079-31: dust   Ex tb IIIC T80 °C Db IP 66/67
                          Inmetro approvals                    TÜV 17.0698 X
                          Ex marking according to EN 60079-0 and EN 60079-1: gas    Ex db IIC T6 Gb
                          Ex marking according to EN 60079-0 and EN 60079-31: dust   Ex tb IIIC T80 °C Db IP 66/67


















        248              You will find detailed product information on our website             Valid as of August 1, 2020
   247   248   249   250   251   252   253   254   255   256   257