P. 251

Isolating Spark Gaps


           EXFS L / EXFS KU
           • For indirect connection / earthing of functionally isolated parts
            of installations under lightning conditions
           • For lightning equipotential bonding according to IEC 62305
            in hazardous areas (zone 2)
           • Corrosion-resistant zinc die-cast enclosure with plastic cover
            and flexible cable connection
           • For bridging insulating joints, insulating flanges, etc. in
            cathodically protected pipe sections
           • Extremely heavy-duty device
           • Approval according to ATEX directive 94/9/EC and IECEx
                                                                                                                      Isolating Spark Gaps


                                                                ATEX and IECEx-certified isolating spark gap for lightning equipotential bonding
                                                                according to IEC 62305 with flexible cable connection.



           EXFS L ...: Isolating spark gap for use in hazardous areas with flexible connecting cable
           EXFS KU:  Isolating spark gap for use in hazardous areas with two 1.5 m long connecting cables for underground installation


           Ex isolating spark gaps of the EXFS L / EXFS KU product line are used when   The approved EXFS L Type with flexible cable connection quickly adapts
           electrically conductive parts of installations cannot be directly intercon-  to any application environment. The prewired spark gaps feature connect-
           nected in hazardous areas, for example, in case of cathodically protected   ing cables of different lengths with cable lug, screw and M10 nut. The flat
           pipeline sections.                                   or angled connection brackets (IF), which are available as accessories,
           ATEX and IECEx-certified EXFS L and EXFS KU spark gaps provide ap-  enable simple connection of the spark gap to pipeline flanges.
           proved safety in accordance with harmonised European standards.  The EXFS KU Type is enclosed by a water-proof PVC sheath and is thus
           The arc-resistant tungsten / copper electrodes ensure a long service life of   ideally suited for underground installation on insulating couplings.
           the Ex spark gaps.





           EXFS L                                                                                           923 060  923 061  923 062   EXFS L100 EXFS L200 EXFS L300
           Ex isolating spark gap for aboveground installation.
                                                                                                            923 060   4013364038899  04 01 05 02   725 g
                                                                                                                  221,80 €
                                                                                                            923 061   4013364038905  04 01 05 02   750 g
                                                                                                              923 062          221,80 € 4013364038912  04 01 05 02   733 g
           Type EXFS ...                        L100            L200            L300
                                                                                                             221,80 €
           Part No.                             923 060         923 061         923 062
           Isolating spark gap according to EN 62561-3 / IEC 62561-3  yes   yes   yes
           Lightning impulse current (10/350 µs)  (Iimp)  50 kA  50 kA          50 kA
           Class (lightning current carrying capability)  N     N               N
           Rated impulse sparkover voltage  (Ur imp)  ≤ 2.5 kV  ≤ 2.5 kV        ≤ 2.5 kV
           Degree of protection                 IP 54           IP 54           IP 54
           ATEX approvals                       DEKRA 11ATEX0146 X   DEKRA 11ATEX0146 X   DEKRA 11ATEX0146 X
           Ex marking according to EN 60079-0 and EN 60079-15: gas  II 3 G Ex nC IIC T4 Gc   II 3 G Ex nC IIC T4 Gc   II 3 G Ex nC IIC T4 Gc
           IECEx approvals                      IECEx DEK 11.0063X   IECEx DEK 11.0063X   IECEx DEK 11.0063X
           Ex marking according to EN 60079-0   Ex nC IIC T4 Gc   Ex nC IIC T4 Gc   Ex nC IIC T4 Gc
           Cable length                         100 mm          200 mm          300 mm



           EXFS KU                                                                                          923 019   EXFS KU
           Ex isolating spark gap with connecting cables for aboveground and underground installation; with water-proof sheath;
           can be shortened to keep cables as short as possible.                                            923 019  kg      4013364033177  04 01 05 02   1.70
                                                                                                              466,80 €

           Type EXFS ...                        KU
           Part No.                             923 019
           Isolating spark gap according to EN 62561-3 / IEC 62561-3  yes
           Lightning impulse current (10/350 µs)  (Iimp)  50 kA
           Class (lightning current carrying capability)  N
           Rated impulse sparkover voltage  (Ur imp)  ≤ 2.5 kV
           Degree of protection                 IP 67
           ATEX approvals                       DEKRA 11ATEX0146 X
           Ex marking according to EN 60079-0 and EN 60079-15: gas  II 3 G Ex nC IIC T4 Gc
           IECEx approvals                      IECEx DEK 11.0063X
           Ex marking according to EN 60079-0   Ex nC IIC T4 Gc
           Cable length                         2x approx. 1500 mm



           Valid as of August 1, 2020                         You will find detailed product information on our website   247