Page 58 - Surge-Protection-E_0.pdf
P. 58

Surge Arresters – Type 2

                         DEHNguard M TT 2P ACI ... FM
        952 121   DG M TT 2P ACI 275 FM
        952 122   DG M TT 2P ACI 385 FM
                         Modular surge arrester with Advanced Circuit Interruption (ACI) for single-phase 230 V-TT and  TN systems (1+1 configuration).
        952 121   4013364376663  04 01 02 24   250 g
              209,90 €
        952 122   4013364387867  04 01 02 24   250 g
              204,40 €
                          Type DG ...                          M TT 2P ACI 275 FM      M TT 2P ACI 385 FM
                          Part No.                             952 121 +               952 122 +
                          SPD according to EN 61643-11 / IEC 61643-11  type 2 / class II   type 2 / class II
                          Max. continuous operating voltage (a.c.) [L-N]  (UC)  275 V (50 / 60 Hz)   385 V (50 / 60 Hz)
                          Nominal discharge current (8/20 µs) [L-N]  (In)  20 kA       20 kA
                          Voltage protection level [L-N] / [N-PE]  (UP)  ≤ 1.5 / ≤ 1.5 kV  ≤ 1.5 / ≤ 1.5 kV
                          Additional external fuse             not required            not required
                          Temporary overvoltage (TOV) [L-N] (UT) – Characteristic   440 V / 120 min. – withstand   440 V / 120 min. – withstand
                          Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic   1200 V / 200 ms – withstand   1200 V / 200 ms – withstand
                          Approvals                            KEMA                    KEMA



                         DEHNguard S ACI ... FM
        952 100   DG S ACI 275 FM
        952 113   DG S ACI 385 FM
                         Pluggable single-pole surge arrester consisting of a base part and plug-in protection module; with Advanced Circuit Interruption (ACI).
        952 100   4013364376526  04 01 02 24   128 g
              128,50 €
        952 113   4013364387874  04 01 02 24   128 g
              136,20 €
                          Type DG ...                          S ACI 275 FM            S ACI 385 FM
                          Part No.                             952 100 +               952 113 +
                          SPD according to EN 61643-11 / IEC 61643-11  type 2 / class II   type 2 / class II
                          Max. continuous operating voltage (a.c.)  (UC)  275 V (50 / 60 Hz)   385 V (50 / 60 Hz)
                          Nominal discharge current (8/20 µs)  (In)  20 kA             20 kA
                          Voltage protection level  (UP)       ≤ 1.5 kV                ≤ 1.5 kV
                          Additional external fuse             not required            not required
                          Temporary overvoltage (TOV) (UT) – Characteristic   440 V / 120 min. – withstand   440 V / 120 min. – withstand
                          Approvals                            KEMA                    KEMA





                         Accessories for DEHNguard modular with Advanced Circuit Interruption (safe dimensioning)
        952 024   DG MOD ACI 275
        952 028   DG MOD ACI 385
                         Switch / Spark Gap Protection Module for DEHNguard ACI
        952 024   4013364377356  04 01 02 24   52 g
              99,60 €
        952 028   4013364387843  04 01 02 24   51 g
              107,40 €    Type                                 DG MOD ACI 275          DG MOD ACI 385
                          Part No.                             952 024 +               952 028 +
                          Max. continuous operating voltage (a.c.)  (UC)  275 V        385 V
                         Spark-gap Based Protection Module for DEHNguard M ACI
        952 022   DG MOD A NPE
        952 022   4013364376533  04 01 02 24   43 g
              99,60 €
                          Type                                 DG MOD A NPE
                          Part No.                             952 022 +
                                                               275 V
                          Max. continuous operating voltage (a.c.)  (UC)
    Surge Arresters – Type 2  952 083  952 083        4013364376540  04 01 02 24   51 g   N-PE Spark-Gap-Based Protection Module for DEHNguard M ACI
          DG MOD H A NPE
         80,90 €
                          Type
                          Part No.                             DG MOD H A NPE
                                                               952 083 +
                          Max. continuous operating voltage (a.c.)  (UC)  275 V
























        54               You will find detailed product information on our website             Valid as of August 1, 2020