Surge Arresters – Type 2
                                                                                                Advance   d Circuit Interruption
                                                                                                ACI
                                                                                                Improved SPD Safety
        DEHNguard modular with Advanced Circuit Interruption (Safe Dimensioning)
                                                             • New technology “Advanced Circuit Interruption” (ACI) inte-
                                                               grated in the protection module, consists of a switch / spark
                                                               gap combination
                                                             • Due to ACI technology no external backup fuse required
                                                             • Small connection cross-sections (6 mm² Cu) absolutely
                                                               sufficient  *)
                                                             • TOV withstand also at 440 V (AC)
                                                             • High system reliability, no tripping of 32 A gG fuses
                                                             • Zero leakage current due to galvanic isolation by ACI
                                                               switch unit
                                                             • Energy coordination with other arresters of the Red/Line
                                                               product family

        For protecting low-voltage consumer installations against surges. For installation   *)   All live conductors should be wired so that they are inherently
        in conformity with the lightning protection zone concept at the boundaries from   short-circuit and earth fault proof
        0B – 1 and higher.


        DEHNguard M TNC ACI 275 FM:  Modular surge arrester with integrated ACI technology for TN-C systems
        DEHNguard M TNS ACI 275 FM:  With integrated ACI technology for TN-S systems
        DEHNguard M TT ACI ... FM:    With integrated ACI technology for TT and TN-S systems (3+1 configuration)
        DEHNguard M TN ACI 275 FM:   With integrated ACI technology for 230 V TN systems
        DEHNguard M TT 2P ACI ... FM:  With integrated ACI technology for 230 V TT and TN systems (1+1 configuration)
        DEHNguard S ACI ... FM:    Modular single-pole surge arrester with integrated ACI technology
        DEHNguard M/S ... ACI ... FM:   With remote signalling contact for monitoring device (floating changeover contact)



        The new modular surge arrester of the DEHNguard ACI product family   TOV withstand: Increase availability
        provides safety at the highest level. This is thanks to ACI technology   Temporary  overvoltages  (e.g.  caused  by  loss  of  neutral)  can  destroy
        (Advanced Circuit Interruption) which replaces the backup fuse with a   conventional  surge protective  devices.  The new DEHNguard  ACI has
        switch / spark-gap combination connected in series with a high capacity   a much better TOV withstand and provides protection without device
        varistor.                                            failure even at 440 V (AC). This increases the availability of your system
        At the end of the service life of the ACI surge arrester, the new technology   and avoids wasting time and money on troubleshooting and repairing
        reduces any fault current to such an extent that not even the smallest   unnecessary damage.
        fuses in the system are tripped. This means much greater availability and
        operational safety for the system in comparison with standard type 2 ar-  Zero leakage current: Increase service lifetime
        resters with external fuses.                         Due to the construction of DEHNguard ACI there s no leakage current.
                                                             This prevents premature ageing of the protective device so that no time
        The new internal arrester backup fuse has further advantages:  and money is wasted on replacement. DEHNguard ACI arresters also con-
                                                             tribute towards operational safety because they prevent the accidental
        Safe dimensioning: Eliminate mistakes                tripping of the insulation monitoring.
        The  new technology  prevents  design errors  which  might  occur  when   Transition in the energy sector: Fulfil future requirements
        dimensioning  or  selecting  overload  protection;  thus  eliminating  the
    Surge Arresters – Type 2  need for a backup fuse. With ACI, protection is directly integrated in the   network parameters change, e.g. as a result of renewable power gen-
                                                             With  ACI arresters you are safely equipped for the future – even if
        arrester and, as a result, optimally adjusted to it. DEHNguard ACI auto-
                                                             eration. Isolated grids and storage systems change the short-circuiting
        matically eliminates the possibility of faulty installation or dimensioning
                                                             conditions.
        errors. The arrester also leaves more space in the switchgear cabinet as
        there is no need for an additional upstream backup fuse. In addition to
        the condition of the varistor, that of the switch / spark-gap combination is   DEHNguard ACI – Maximum system availability
        also signalled and notified via the tried and tested mechanical operating   System downtimes caused by an upstream safety device tripping or
        state / fault indicator.                             being switched back on are a thing of the past. This means much greater
                                                             availability and operational safety for the system in comparison with
        Conductor cross-section of only 6 mm²: Easier to install  standard type 2 arresters with external fuses.
        A conductor cross-section of 6 mm² is always enough for the active con-
        ductors and PE. You save the valuable time you would, in the past, have
        spent dimensioning the cross-sections. 6 mm² Cu also makes installation
        easier because the bending radiuses are smaller. DEHNguard ACI there-
        fore allows shorter wiring.