SAFETY
EARTHING & SHORT-CIRCUITING
EARTHING & SHORTCIRCUITING LEADS MADE AND TYPE TESTED TO IEC61230
Short Circuit Withstand rating of cable in Irms
Cable Cross
Section 1 sec ≤ 0.5 sec
16mm² 3.2kA 4.5kA
25mm² 4.9kA 7kA
35mm² 6.9kA 10kA
50mm² 9.9kA 14kA
70mm² 13.8kA 19.5kA
95mm² 18.7kA 26.5kA
120mm² 23.7kA 33.5kA
150mm² 29.6kA 42kA
SURGE
PROTECTION
Configure your own customised Earthing and
Shortcircuiting device by visiting:
WWW.DEHN.DE/EN/EUK
8 EASY STEPS:
1 - Select configuration view:
a. Product View
b. System View
2 - Define the structure of your earthing and shortcircuiting device, i.e. 1 pole, 3 Pole, 4 Pole etc.
3 - Define phase end cable cross section based on required withstand characteristics of your installation.
4 - Determine your Earth end cable cross section.
5 - Select the phase end clamp based on your preference or type of earth points available at your installation.
6 - Specify Earth end termination or clamp.
7 - Select a relevant earthing stick if required or skip to next step.
8 - PDF your selection and email to [email protected] for a quote within 2 working days.