MV FUSE LINKS
MV DIN PROTECTION FUSES - OUTDOOR 6 - 12kV
Features: Rated Minimum Barrel Length
- Back-Up Protection 6kV to 12kV. Current Breaking Diameter a
- Suitable for indoor or outdoor switchgear. (A) Current (A) (mm) (mm) Part No.
- Breaking capacity 63kA. 1.0 14 45DB120V1P
- Complies to IEC60282-1. 2.0 16 45DB120V2P
- Medium trip indicators. 4.0 22 45DB120V4P
6.3 30 45DB120V6.3P
10 42 45DB120V10P
16 54 45DB120V16P
20 73 56 45DB120V20P
25 93 45DB120V25P
31.5 105 292 45DB120V31.5P
45DB120V80P 40 125 45DB120V40P
Definition: 50 160 45DB120V50P
Back-up fuse links have a rated minimum 63 230 45DB120V63P
breaking current from which the fuse links are 80 350 65 45DB120V80P
able to interrupt current. 100 500 78 45DB120V100P
Back-up fuse links are not supposed to operate 125 480 45DB120V125P
below their minimum breaking current. 160 560 88 45DB120V160P
200 610 45DB120V200P
Features: MV DIN PROTECTION FUSES - OUTDOOR 10 - 24kV
- Back-Up Protection 10kV to 24kV. Rated Minimum Barrel Length
- Suitable for indoor or outdoor switchgear. Current Breaking Diameter a
- Breaking capacity up to 63kA. (A) Current (A) (mm) (mm) Part No.
- Complies to IEC60282-1. 1.0 14 45DB240V1P
- Medium trip indicators. 2.0 16 45DB240V2P
4.0 23 45DB240V4P
6.3 30 45DB240V6.3P
10 43 45DB240V10P
16 60 56 45DB240V16P
20 76 45DB240V20P
25 93 45DB240V25P
31.5 105 442 45DB240V31.5P
40 130 45DB240V40P
50 205 45DB240V50P
45DB240V25P 63 280 45DB240V63P
80 310 65 45DB240V80P
100 430 78 45DB240V100P
125 760 45DB240V125P*
160 900 88 45DB240V160P*
200 1050 45DB240V200P*
*31.5kA breaking capacity.
Fuse clips with retaining spring. suit 45mm Ø diameter HVDCC
HVDCC