EXT56
           OUTDOOR SWITCHBOARD SOLUTIONS


          GENERAL DATA

           Applications              Low voltage power switchgear and control gear assemblies, power distribution boards, Motor control
                                     centres, PLC & DCS panel boards.
           Installation              Outdoor.
           Mounting possibilities    Floor Standing.
           Standard Colours          RAL 7032 Grey / RAL 2000 Orange frame and X15 / RAL 7032 Grey / Sand finish aluminium cladding*.
           Standard                  AS/NZS 61439-1:2016.
           Coating                   Epoxy / Polyester powder, Thickness > 50 μm smooth.
           Material                  Frame : 2mm electrogalvanized mild steel*.
                                     Frame collar : 2mm Marine grade aluminium 5052 H32*.
                                     Doors, Covers and Rainhoods : 3mm Marine grade aluminium 5052 H32*.
                                     Plinth : 3mm mild steel hot dipped galvanized.
           * Powder coated cladding on request.









          MECHANICAL DATA
           Field / Tier Arrangement  Front connected.
           Cable entry               Bottom.
           Compartment types         Fixed.
           Access                    Front / Rear.
           IP rating                 IP56 (Outdoor).
           Form of segregation       1, 2a, 2b, 3a, 3b, 4a, 4b.
           Maximum dimensions of a transport   Width - 2400mm (Extendable).
           section (Basic module 200x200x200)  Height - 2000mm (Maximum).
                                     Depth - 800mm.







          ELECTRICAL DATA

           Rated operational voltage (Ue)  Up to 1000V.
           Rated frequency (f)       50Hz.
           Rated impulse voltage (Uimp)  Up to 12 kV.
           Rated current (In) for TM   Up to 3200A (Refer to the Elsteel CM for more information).
           panels(Uimp)
           Rated short time current (lcw)  Up to 100kA/1s & 80kA/3s (Refer to the Elsteel CM for more information).
           Min. clearance and creep age  (Refer to the Elsteel CM for more information).
           Earthling systems         TN-C, TN-S, TN-C-S, TT, IT.
           Internal Arcing Fault Containment  Acc. to AS/NZS 61439-1:2016 Appendix ZD.










    246   V16-PD-SBS-R01                                www.ipd.com.au                             Phone: 1300 556 601
   249   250   251   252   253   254   255   256   257   258   259