Page 323 - V16 Catalogue Final
P. 323
DIGIWARE PLUG AND PLAY AC METERING SYSTEM
CURRENT SENSORS (CT’S)
SPLIT-CORE CURRENT SENSORS
Features: Model Nominal Current Range (A) Actual Coverage Range (A) Part No. POWER
- Extended measurement range: 2% to 120% of nominal TR-10 25-63 0.5...75.6 48290555 MONITORING
current range. 48290556
- CT accuracy Class 0.5. TR-14 40-160 0.8...192
- Plug & Play, RJ12 connection. TR-21 63-250 1.26...300 48290557
- Safe disconnection of CT secondary under load. TR-32 160-600 3.2...720 48290558
- Smart sensors.
SPLIT-CORE CURRENT SMART SENSORS
iTR SENSORS ENABLE THE USER TO MONITOR ON/OFF/TRIP STATUS OF
UPSTREAM CIRCUIT BREAKER
TR Split-Core Current Sensors
Model Nominal Current Range (A) Actual Coverage Range (A) Part No.
Featues: iTR-10 25-63 0.5...75.6 48290655
- Extended measurement range: 2% to 120% of nominal iTR-14 40-160 0.8...192 48290656
current range.
- CT accuracy class 0.2. iTR-21 63-250 1.26...300 48290657
- Plug & play, RJ12 Connection. iTR-32 160-600 3.2...720 48290658
- Safe disconnection of CT secondary under load.
- Smart Sensors.
- Virtual Monitor.
- AutoCorrect technology.
iTR...
DIMENSIONS - TR/iTR
Model H x W x D (mm) Ø (mm) A B
TR-10 / iTR-10 44 X 26 X 28 10 - -
TR-14/ iTR-14 67 X 29 X 28 14 14 15
TR-21 / iTR-21 65 X 37 X 43 21 21 23
TR-32 / iTR-32 86 X 53 X 47 32 32 33
TR/ iTR-10, TR/iTR-14, TR/iTR-21, TR/iTR-32
Phone: 1300 556 601 www.ipd.com.au V16-PM-R04 315