Page 333 - V16 Catalogue Final
P. 333
CURRENT TRANSFORMERS SELECTION CHART
SPLIT CORE CT
POWER
MONITORING
Model TO23 TO58 TO812 TO816
Current Ratio Up to 200/5 Up to 800/5 Up to 1500/5 Up to 5000/5
Accuracy Class 3 1, 0.5 0.5 0.5
Conductor Type Cable & Bar Through Cable & Bar Through Cable & Bar Through Cable & Bar Through
Aperture (mm) 23 x 33 55 x 85 85 x 125 85 x 125
SOLID CORE CT
Model TCA14 TCA21 TCB26-30
Current Ratio 50/5 Up to 300/5 Up to 600/5
Accuracy Class 1 1, 0.5 1, 0.5
Conductor Type Cable-Through Cable-Through Cable/Bar through
Aperture (mm) ø14 ø21 ø26/10.5 x 30.5
Model TCB44-50 TCB44-63 TCB85-100
Current Ratio Up to 1200/5 1250/5 Up to 3000/5
Accuracy Class 0.5 0.5 0.5
Conductor Type Cable/Bar through Cable/Bar through Cable/Bar through
Aperture (mm) ø44/12.5 x 50.5 ø44/10.5 x 63.5 ø85/31 x 101
3 IN 1 SOLID CORE CT
Model 192T3310 192T3425
Current Ratio Up to 3 x 250/5 Up to 3 x 600/5
Accuracy Class 1 1
Conductor Type Cable/Bar through Cable/Bar through
Aperture (mm) ø18/5 x 20 ø22/10 x 30
CTME SERIES CT
Model CTME-1 CTME-2 CTME-3 CTME-4 CTME-5 CTME-6
Current Ratio Up to 100/5 Up to 400/5 Up to 1200/5 Up to 2000/5 Up to 2500/5 Up to 4000/5
Accuracy Class 2,3,5 1,3,5 0.5,1,2 0.5,1 0.5 0.5
Conductor Type Cable-Through Cable-Through Cable/Bar through Cable/Bar through Cable/Bar through Cable/Bar through
Apeture (mm) ø22 ø33 ø48 ø82 ø82/20.8 x 102 ø126.5/58 x 126.5
- Refer Page 418 for current switches.
Phone: 1300 556 601 www.ipd.com.au V16-PM-R04 325