AF CONTACTORS
           4 TO 630kW


                                               3 POLE - 3NO CONTACTORS
          Features:                              400V AC-3  400V AC-3    AC-1          Auxiliary
          - 3 Pole.                                (kW)        (A)        (A)       NO        NC    Part No.
          - Add-on auxiliary contact.                                                1        0     AF093010
          - Built-in surge suppression.             4          9          25
          - Reduced panel energy consumption.                                        0        1     AF093001
          - Very distinct closing and opening.     5.5         12         28         1        0     AF123010
          - DIN or Panel mounting.                                                   0        1     AF123001
                                                                                     1        0     AF163010
                                                   7.5         18         30
                                                                                     0        1     AF163001
                                                    11         26         45         0        0     AF263000    1)
                                                    15         32         50         0        0     AF303000    1)
                                                               38         50         0        0     AF383000    1)
                                                   18.5
                                                               40         70         0        0     AF403000
                                                    22         53        100         0        0     AF523000
                                                    30         65        105         0        0     AF653000
                                                    37         80        125         0        0     AF803000
                                                    45         96        130         0        0     AF963000
                       AF093010...                  55        116        160         1        1     AF1163011




          Features:                                                                    Auxiliary
          - 3 Pole.                              400V AC-3  400V AC-3    AC-1       NO        NC    Part No.
                                                   (kW)
                                                                          (A)
                                                               (A)
          - Add-on auxiliary contact.
          - Built-in surge suppression.             75        140        200         1        1     AF1403011
          - Reduced panel energy consumption.       75        146        225         1        1     AF1463011
          - Very distinct closing and opening.      90        190        275         1        1     AF1903011
          - Can withstand short voltage dips and voltage sags.  110  205  350        1        1     AF2053011
          - For connection with built-in cable clamps.  140   265        400         1        1     AF2653011
          - Panel mounting.                        160        305        500         1        1     AF3053011
                                                   200        370        600         1        1     AF3703011
                                                   220        400        600         1        1     AF4003011  *
                                                   250        460        700         1        1     AF4603011  *
                                                   355        580        800         1        1     AF5803011  *
                                                   400        750        1050        1        1     AF7503011  *
                                                    –          –         1260        1        1     AF12503011  *
                                                   475        860        1350        1        1     AF13503011  *
                                                   560        1060       1650        1        1     AF16503011  *
                       AF1163011...
                                                    –         1060       2050        1        1     AF20503011  *
                                                    –          –         2650        1        1     AF26503011  *


                                                  To complete Part Number, add the required voltage code:
                                                Code         11                 13                 14
                                                Control Voltages  24…60V AC / 20…60V DC  100…250V AC/DC  250…500V AC/DC

                                                *  Code      70
                                                Control Voltages  100…250 V AC/DC
                       AF3703011...            1) 11 (24..60V AC/20..60V DC) arrangement not suitable for direct control by PLC-output.
                                               - Other coil voltages and auxiliary contact arrangements available.
                                               - AF400 ... AF2650 are equipped with low voltage inputs for control, for example by a PLC. For example, a
                                                240V AC supply can be permanently on A1 and A2 which allows the contactor to be switched with a 24V
                                                DC signal from a PLC.









    350   V16-IC-C&O-R04                                www.ipd.com.au                             Phone: 1300 556 601